8. Log-in to your Honeywell LCBS Connect account.
NOTE: www.lcbs.honeywell.com
9. Add the gateway under a building in the portal.
10. Make sure you enter the correct Registration ID.
Registration IDs are case-sensitive.
11. After you have added the gateway under a building
account, the gateway will automatically start send-
ing controller data to the cloud. The BLUE LED will
be SOLID ON if the gateway is able to send data to
Honeywell Cloud.
NETWORKING
• IP allocation requires a DHCP server, provided
automatically by most firewall routers.
• Firewall configuration requires port 443 or 5671
(optional).
• Gateway does not work behind an HTTP proxy and may
not work behind a transparent proxy, especially if it
requires authentication.
Refer to "Honeywell LCBS IT White Paper" for further
details.
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the
FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential
installation. This equipment generates uses and can radiate radio frequency energy and, if not installed and used in
accordance with the instructions, may cause harmful interference to radio communications. However, there is no
guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference
to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to
try to correct the interference by one or more of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and receiver.
- Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
This device complies with Part 15 of the FCC rules. Operation is subject to the following two conditions: (1) this device
may not cause harmful interference, and (2) this device must accept any interference received, including interference
that may cause undesired operation.
This Class B digital apparatus complies with Canadian ICES-003.
Cet appareil numérique de la classe B est conforme à la norme NMB-003 du Canada.
This device complies with Industry Canada license-exempt RSS standard (s). Operation is subject to the following two
conditions: (1) this device may not cause interference, and (2) this device must accept any interference, including
interference that may cause undesired operation of the device.
SPECIFICATIONS
Dimensions: See Fig. 1
ELECTRICAL
Rated Voltage: 20-30 VAC, 50/60 Hz, 10 VA; 24 VDC, 1.25 A
NEMA-2 Class 2 power limited device
ENVIRONMENTAL RATINGS
Operating: 32 F – 120 F (0 C – 50 C)
Shipping and Storage: -40 F – 150 F (-40 C – 66 C)
Relative Humidity: 5% to 95% non-condensing
Enclosure Rating: IP-20, NEMA-1
OPERATION
Power Failure Backup: 24 hours at 32 to 100° F (0 to 38°
C), 22 hours at 100 to 122° F (38 to 50° C)
DEVICE CONNECTIONS
Power: 24 VDC Wall Wart or 24 VAC input
Ethernet: One (1) Ethernet interface supporting 10 Base-
T and 100 Base-TX
Network: LONworks™
APPROVAL BODIES
CUL, US listed E87741 UL916 energy management
equipment subassembly
RoHS compliance: 2011/65/EC and EN 50581:2-12
3
LCBS CONNECT GATEWAY
31-00081—03