Technical Specifications (24x)
•
Cable: Belden (shielded) 8777, 9873, 9773
•
Certifications: FCC Part 15; CE Mark, and UL 294
•
Color: Gray
•
Dimensions with backplate (height/width/depth): 4.37" x 3.31" x
1.10" (110.99 x 84.07 x 27.94 mm)
•
Environments: interior or exterior
•
Humidity Range: 5 to 95%, non-condensing
•
Index of Protection: IP 65 (IEC 529)
•
12-button (3 x 4 matrix) tactile membrane keypad (Model 245 only)
•
Microcontroller Communications: F/2F supervised door input, REX,
and reader communication/power monitoring
•
Minimum Wiring: 4 conductors
•
Operating Temperature/Range: -35 to 151
•
Power supply: 8 - 30 VDC (see requirements below)
•
Weight: 5.6 oz (158.75 g)
Table 8: Currents, Ranges, and Distances
Supply Voltage
Current
Cable Gauge
Distance
Note: With the exception of the Power, Common/Ground, Reader Data
Lines and External Green LED Circuit, all other wiring is limited to
same-room installations or no more than 20 feet.
Cable Distance
12 VDC
200 mA @12 VDC
18 AWG
22 AWG
2,041 ft.
856 ft.
(622 m)
(261 m)
GE Contactless Reader Model 24x/250
o
o
F (-35 to 66
C)
13.6 VDC
18 AWG
22 AWG
3,123 ft.
1,309 ft.
(952 m)
(399 m)
23