Fire Alarm Control Panel PL-1000
In the example shown, the I/O associations are:
A
Fault will immediately activate Sounder Circuit 1
B
Evacuation will immediately activate: Sounder Circuit 1, Output Modules 001 and 002
C
Output Module 001 will be activated by:
Evacuation command
One device in alarm from Zone 2 and one device in alarm from Zone 3
One device in alarm from Zone 5 once delay time is finished
D
Output Module 002 will be activated by:
Evacuation command
One device in alarm from Zone 1
Two devices in alarm from Zone 4
One device in alarm from Zone 5 once delay time is finished
44
M-169.1-SERIE-PL-EN / 09.2022