13.7 Configuration – matrix / Cause and Effect I/O Matrix
In this menu, you can associate the Zones General Fault events and Evacuation to the panel sounders and to the addressable outputs. The association happens simply
clicking on the dot that cross the Zone/Function inputs and the outputs.
 Dots meaning:
Empty
The Input and the output ARE NOT associated
Full
The Input and the output ARE associated
Half Full / Half Empty
At least two Zones with the same selection half full/empty are required to be in alarm to activate the relevant output
(double consent Cross-Zone)
+
At least two devices related to the same Zone associated to the output must be in alarm to activate the relevant output
(double consent Single Zone)
It indicates that the Output will be activated once the countdown of the delay time configured into the Panel Configuration
menu is finished. The Delay Override option is automatically enabled on the main screen menu, and you can override the
delay time at any time pressing the button