6

CBXi Operation

PHYSICAL LAYOUT

DIMENSIONS

WIRING

CAUTION - DANGER OF EXPLOSION IF BATTERY IS INCORRECTLY
REPLACED.
REPLACE ONLY WITH THE SAME OR EQUIVALENT TYPE RECOMMENDED
BY THE MANUFACTURER. DISPOSE OF USED BATTERIES ACCORDING TO
THE MANUFACTURER'S INSTRUCTIONS.
Supply Requirements
Supply Rating
CBXi
CBXi + 1 x FLX
CBXi + 2 x FLX
CBXi + 3 x FLX
FLX Power Connection
Auxiliary Power
BACnet Loading
©ABB 2022 All Rights Reserved.
Subject to change without notice
WWW.CYLON.COM
CBXi IP Controller |
24 V AC ±20 % 50/60 Hz
30 VA (no FLX modules)
42 VA
54 VA
66 VA
Proprietary FLX bus connector
carries power and comms from
CBXi-8R8 unit. CBX-8R8 can supply
power to up to 3 FLX modules.
18 V DC / 60 mA output
¼ unit load device
CBXi Operation
Ground
Common
Point Numbers
Terminal
Numbers
Relay Common
(24 V only)
63