Ma-2000 Cpu Board - Honeywell MA-2000 Installation Manual

Hide thumbs Also See for MA-2000:
Table of Contents

Advertisement

6.1 MA-2000 CPU Board

JDSPE
Earth
JDSPEA
Dispersion
JDSPEB
JDSPEC
Clip / HON
J1
Protocol
Fault Relay
Possibility of NO/NC contact selection through JGST
Relay Alarm,
Possibility of selection for each relay: potential-free contact NO/NC or as controlled output with
User1 and
47 KΩ, 5 % balance or diode termination, via JALL, JUSR1, JUSR2
User2
Firmware Update
1
OFF
DIP SW3
ON
ON
ON
Configuration Serial Port 3
1
DIP SW4
ON
OFF
Configuration Serial Port 2
1
DIP SW5
ON
OFF
M-167.1-MA2000-EN / 06.2022
Jumper housed on AW80Usx. Removing the JDSPE jumper causes the control panel
to ignore a ground fault on the control panel circuits, loop lines, and isolated CanBus
lines.
Removing the JDSPEA jumper causes the control unit to ignore an RS485-1 ground
fault (isolated).
Removing the JDSPEB jumper causes the control unit to ignore a RS485/RS232 -2
ground fault (isolated).
Removing the JDSPEB jumper causes the control unit to ignore a RS485/RS232 -3
ground fault (isolated).
Clip: Set J1 to position 2-3
2
3
4
OFF
OFF
OFF
Normal Operating setting
Copy the configuration in the USB memory key
OFF
OFF
OFF
ON
Restore factory configuration
OFF
OFF
ON
ON
ON
from USB memory key loads configuration previously prepared by PK SW Tool
2
3
4
ON
Serial Port 3 type RS232
OFF
OFF
ON
ON Serial Port 3 type RS485
OFF
2
3
4
ON
Serial Port 2 type RS232
OFF
OFF
ON
ON Serial Port 2 type RS485
OFF
Board Setup
HON: Set J1 to position 1-2
MA-2000
19

Advertisement

Table of Contents
loading

This manual is also suitable for:

Morley-ias ma-8000