Honeywell PW Series Installation Instructions page 3

Conduit wet pressure transmitters

Advertisement

IMPORTANT
DO NOT attempt to plumb or tighten the sensors while wires
are attached, as you risk pulling wires from cable attachments.
8. Wire sensors A & B to the PWTB Transmitter terminals
labeled A & B respectively. See the table in point 6 if
wiring a pre-ordered cable length for color coordination.
For strain relief, tighten cable glands.
SENSOR A
Figure 4. PWTB Transmitter Terminals
IMPORTANT
Cable shielding should be connected to the Shield
terminal at the PWTB transmitter and left
unconnected at the sensor element end.
9. Connect conduit fittings to the sensors and PWTB
transmitter. Use water-tight fittings if required by your
installation conditions.
10. Wire PWTB transmitter for voltage or current output as
shown (Remote zero wiring is optional):
Figure 5. Transmitter Output/Remote Zero Wiring
11. Select 20 mA, 5 V, or 10 V output using the OUTPUT
switch based on wiring configuration.
4-20mA
0-5V
0-10V
SENSOR B
PWR
RTN
V
ZERO
ZERO
PW SERIES CONDUIT WET PRESSURE TRANSMITTERS
12. Configure output range and sensor PSIG using DIP
switches 1-7. DIP 1-3 set the sensor PSIG corresponding
to the PWTB ordered. DIP 4-7 are used to set the desired
output signal range. Both use the binary code system
outlined in the table.
Table 1. PWB Transmitter DIP Switch Configuration
DIP
1
2
3
4
5
6
7
8
9
10
11
12
DIP
Binary
000
011
1-3
100
110
DIP
Binary
0011
0100
0101
0110
0111
1000
4-7
1001
1010
1011
1100
1101
1110
13. Inspect the LCD for readings. The LCD toggles between
sensor A, sensor B, and PSID reading.
• A dash mark at the top left of the LCD indicates the
reading of sensor A.
• A dash mark at the bottom left of the LCD indicates
the reading of sensor B.
• PSID reading is displayed without any mark at the
left of the LCD.
14. O/R symbol will flash in the bottom center of the LCD if
the differential pressure reading is over range. Select a
larger PSID range to avoid clipping of readings if this
occurs.
3
Function
DOWN
SENSOR2
0 (off)
SENSOR1
0
SENSOR0
0
RANGE3
0
RANGE2
0
RANGE1
0
RANGE0
0
Units
KPA
UNI/BI
BI
MODE
FAST
SWAP
B-A
ABS
ABS
Sensor (PSIG)
Sensor (kPa)
Test
50
100
250
Range (PSIG)
Range (kPa)
0-10
0-15
0-20
0-25
0-30
0-40
0-50
0-75
0-100
0-125
0-150
0-250
31-00539-01
UP
1 (on)
1
1
1
1
1
1
PSI
UNI
SLOW
A-B
+/-
Test
345
689
1724
0-69
0-103
0-138
0-172
0-207
0-276
0-345
0-517
0-689
0-862
0-1034
0-1724