2.3
M+Model_SetLoggingParam (Logging function
setting)
No.
Name
1
M+FX5-4AD_SetLoggingParam
2
M+FX5-8AD_SetLoggingParam

Overview

Turning on i_bEN (execution command) allows the logging function of a specified channel to be set.
M+FX5-4AD_SetLoggingParam
(1)
B
:
i_bEN
(2)
DUT
i_stModule
:
(3)
UW
:
i_uCH
(4)
B : i_bLogEnable
(5)
UW
:
i_uLogData
(6)
UW
:
i_uLogCycleVal
(7)
UW
:
i_uLogCycleUnit
(8)
UW
:
i_uLogPoints
(9)
UW
:
i_uLogTrigCond
(10)
UW : i_uLogTrigData
(11)
W
:
i_wLogTrigValue
(12)
UW
:
i_uUnitType

Labels

Input label
No.
Variable name
Name
(1)
i_bEN
Execution command
(2)
i_stModule
Module label
(3)
i_uCH
Target channel
(4)
i_bLogEnable
Logging enable/
disable setting
(5)
i_uLogData
Logging data setting
o_bENO
:
B
(13)
o_bOK
:
B
(14)
o_bErr
B
(15)
:
(16)
o_uErrId
:
UW
Data type
Range
Bit
ON, OFF
Structure
The setting range
differs depending on
the module label.
Word [Unsigned]/Bit
■FX5-4AD
String [16-bit]
1 to 4
■FX5-8AD
1 to 8
Bit
ON, OFF
Word [Unsigned]/Bit
0: Digital output
String [16-bit]
value
1: Digital operation
value
2 ANALOG INPUT MODULE, MULTIPLE INPUT MODULE FB
Target module
FX5-4AD
FX5-8AD
Description
ON: The FB is activated.
OFF: The FB is not activated.
Specifies the module label for the analog input/multiple
input module.
Specifies a channel number.
ON: Enables the logging function.
OFF: Disables the logging function.
Sets the data to be logged.

2.3 M+Model_SetLoggingParam (Logging function setting)