FIGURE 3. TYPICAL 2-WIRE INITIATING CIRCUIT CONFIGURATION, NFPA STYLE B:
ANY NUMBER OF UL LISTED
CONTACT CLOSURE DEVICES
MAY BE USED. DO NOT MIX FIRE
ALARM INTIATING, SUPERVI-
SORY, OR SECURITY DEVICES
ON THE SAME MODULE.
47K EOL
RESISTOR
ELR-47K
INITIATING DEVICE CIRCUIT (IDC) - NFPA STYLE B
POWER LIMITED: 450µA MAX. @ 11 VDC MAX
INSTALL CONTACT CLOSURE DEVICES PER
MANUFACTURER'S INSTALLATION INSTRUCTIONS.
FIGURE 4. TYPICAL 4-WIRE FAULT TOLERANT INITIATING CIRCUIT CONFIGURATION, NFPA STYLE D:
TO NEXT
ANY NUMBER OF UL LISTED
CONTACT CLOSURE DEVICES
MAY BE USED. DO NOT MIX FIRE
ALARM INTIATING, SUPERVI-
SORY, OR SECURITY DEVICES
ON THE SAME MODULE.
EOL RESISTOR
IS INTERNAL AT
TERMINALS 8
AND 9
INSTALL CONTACT CLOSURE DEVICES PER
MANUFACTURER'S INSTALLATION INSTRUCTIONS.
Velociti
®
, Gamewell-FCI
®
, System Sensor
®
, and Honeywell
TO NEXT
DEVICE
MONITOR
MODULE
DEVICE
MONITOR
MODULE
®
are registered trademarks of Honeywell International, Inc.
ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED
ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED
2
FROM PANEL OR
PREVIOUS DEVICE
CONNECT MODULES TO LISTED
COMPATIBLE CONTROL PANELS ONLY
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX.
TWISTED PAIR
IS RECOMENDED
FROM PANEL OR
PREVIOUS DEVICE
CONNECT MODULES TO LISTED
COMPATIBLE CONTROL PANELS ONLY
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX.
TWISTED PAIR
IS RECOMENDED
©2017 Honeywell. 02-10
C1021-00
C1022-00
I56-3553-003