3.5. Location

The location of the HVC-R 100/150 E-Bus Charger must meet the following requirements:
The height is not more than 2000 m above sea level.
The HVC-R 100/150 E-Bus Charger must not be immersed in water, or any other fluid.
The operational temperature of the HVC-R 100/150 E-Bus Charger is between -35 and
55 ⁰C.
For locations where the Power Cabinet will be exposed to direct sunlight and
high ambient temperatures for most of the day, it is recommended to install
protection from direct sunlight. Otherwise, the temperature inside the cabinet
might exceed the maximum temperature.
Do not install or use the HVC-R 100/150 E-Bus Charger in areas where there is an
explosion hazard. You must provide information about the HVC-R 100/150 E-Bus
Charger to the fire brigade.
The protection rating of the housing of the Power Cabinet is IP54 and the Dual Depot
Charge Box is IP65 (excluding charge cable) and designed for outdoor use.
It is recommended to provide good lighting around the charge system to increase
safety.
Design and arrange the location around the HVC-R 100/150 E-Bus Charger on a
matter that the Dual Depot Charge Box and the Power Cabinet are hit by a vehicle is
as small as possible. For example, bollards can be installed (see picture below) around
the Power Cabinet and crash protection elements can be fitted to the concrete
foundation (see section Concrete foundation for the pedestal on Page 43).
Document: v0.4 / Document No.: TBA | Date: 11-08-2021
Power Cabinet secured with bollards
HVC-R 100/150 E-Bus Charger Installation Guide