14002573-001 HP970 Humidistat and
TP970 Thermostat Modernization Kit
This Modernization Kit contains the parts required to convert
fittings for one- and two-pipe thermostats and humidistats to
C O V E R P L A T E
W I T H P A P E R I N S E R T
APPLICATION
Table lists which Honeywell Humidistat/Thermostat to
use as a replacement and which figure to refer to for
replacement procedures.
Table
Honeywell Inc.
Copyright
1989
FOAM SPACER
Fig.
Modernization kit parts.
Humidistat/thermostat replacement and figure number cross-reference.
Honeywell
All
Rights Reserved
accept TP970 Thermostats and HP970 Humidistats (Fig. 1).
The Humidistat/Thermostat and cover are ordered separately.
Honeywell
DECORATIVE
WALL RING

Advertisement

loading

Summary of Contents for Honeywell 14002573-001

  • Page 1 W I T H P A P E R I N S E R T WALL RING FOAM SPACER Fig. Modernization kit parts. APPLICATION Table lists which Honeywell Humidistat/Thermostat to use as a replacement and which figure to refer to for replacement procedures. Table Humidistat/thermostat replacement and figure number cross-reference. Honeywell Honeywell Inc.
  • Page 2 stat replacement and figure number cross-reference. (continued) Powers HS & D Powers T21 mullion application does not require the odernization K i t . INSTALLATI NOTES: This Kit contains more parts than will be used on any 4. When replacing a one-pipe device, the restrictor must installation.
  • Page 3 14002573-001 HP970 HUMIDISTAT AND TP970 THERMOSTAT MODERNIZATION KIT DECORATIVE , W A L L R I N G - ‘ - - B L A C K SPACER RING Fig. 2. Decorative wall rng and black spacer ring modification for surface run tubing.
  • Page 4 14002573-001 HP970 HUMIDISTAT AND TP970 THERMOSTAT MODERNIZATION KIT Prepare Location For Humidistat/ Thermostat Remove and discard the old Thermostat/Humidistat and rings. Remove the tubing from the fitting. Clean the fitting, if required. Determine the appropriate installation figure number reference from Table Identify and install the correct mounting parts according to the figure number determined in Step 4.
  • Page 5 COLLECT PARTS FROM BAG AND ASSEMBLE. (EITHER HOLE) (USE HOLE OPPOSITETOP MOLE) SHEET METAL (2) USE SLOTS...
  • Page 6 MAIN...
  • Page 7 14002573-001 HP970 HUMlDlSTAT AND TP970 THER NEAR C~N~~CTO~. ~~CATET~~E CLAMP SPRINGS AND BARB INSERT ADAPTER. INSTALL REQUIRED MOUNTING PARTS. Fig. 9. Honeywell T Fig. 8. Honeywell TP901 A, B replacement.
  • Page 8 TP970 THERMOSTAT MODERNIZATI 14002573-00 I HP970 H MORTAR JOINT FLUSH BANJO COLLECT OR 2 AIR HEAD, LENGTH, AND DISCARD CONNECTOR END. 10 OR ‘NOTCH FOR TUBING AS REQUIRED. 911A,TP913,TP923A, B, lacement. 95-7135...
  • Page 9 14002573-001 HP970 HUM/D/STAT AND TP970 THERMOSTAT MODERNIZATION KIT FLUSH FITTING FLUSH FITTING COLLECT PARTS FROM BAG AND ASSEMBLE. COLLECT PARTS FROM BAG AND ASSEMBLE. INSTALL ADAPTER. INSTALL ADAPTER. x IN. (2) NO. 6 x IN. (2) REQUIRED MOUNTING PARTS. INSTALL REQUIRED MOUNTING PARTS.
  • Page 10 HP970 TP970 THERMOSTAT MODERNIZATION KIT FLUSH BOX SURFACE FITTING CUTTUBING NEAR CONNECTOR. LOCATETUBE CLAMP CUTTUBING NEAR CONNECTOR, CLAMP SPRINGS. NOTE: WAREHOUSE PARTS 1459 AND ORDERED SEPARATELY. SPRINGS AND BARB CONNECTORS. SPRINGS (2) CONNECTORS (2) TUBE CLAMP SPLICE PLASTIC TUBING. SPLICE PLASTIC TUBING TO WlTH WAREHOUSE ADAPTERS.
  • Page 11 14002573-001 HP970 HUMIDISTAT AND TP970 THERMOSTAT MORTAR JOINT FLUSH BOX BRANCH MAIN CUTTUBING NEAR CONNECTOR. LOCATETUBE CLAMP COLLECT PARTS FROM BAG AND ASSEMBLE. AND BARB CONNECTORS (2). CLAMP INSTALL ADAPTER. SPLICE PLASTlC TUBING. NO. 5 x IN. (2) INSTALL REQUIRED PARTS.
  • Page 12: Calibration Check

    14002573-001 HP970 HUMIDISTAT AND TP970 THERMOSTAT MODERNlZATlON KIT Calibration Check Measure the rh with a Digital Relative Humidity Indicator Pen CCT915 or other accurate rh measuring device, Digital Relative Humidity indicator Pen CCT915 or other Turn the setpoint adjustment until the setpoint indicator...
  • Page 13 NOTES: Turn the setpoint indicator adjustment down (DA) or up The Thermostats are accurately factory calibrated and (RA) until the setpoint indicator reads 5 degrees F (2.8 should require only the CHECK to degrees C) below (DA) or above (RA) room ensure correct operation”...
  • Page 14 0 psi (0 kPa) (RA) or 13 psi (90 kPa) (DA). TP972A: 0 psi (0 kPa). If it does not, turn the switchover adjustment screw (Fig. 20) clockwise until it does. range to within degrees F Turn the switchover adjustment screw counterclockwise pecified throttling range for until the pressure begins to: either the throttling range...
  • Page 15 14002573-001 HP970 HUMIDISTATAND TP970 THERMOSTAT MODERNIZATION KIT Humidistat/Thermostat Cover Mounting Remove the caution card from the cover. Select the correct window (vertical or horizontal/dual or STAT BACKPLATE blank) and peel the release liner from window back. UTION Before installing the window, carefully check the window selection and orientation.
  • Page 16 By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use or modification to, the literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against any liability, cost, or damages, including attorneys’ fees, arising out of, or resulting from, any modification to the literature Honeywell by you.