Connectors And Cabling; Input Power - GE PACSystems RXi Box IPC User Manual

Table of Contents

Advertisement

Chapter

Connectors and Cabling

4
This chapter describes the connector layout and cabling requirements on the RXi box IPC. Power
and communication connectors are described in this section.
All connectors are provided on the bottom panel of the IPC.
Summary of Cabled Ports
24 VDC
Ethernet 1
Ethernet 2
RS-232 Serial
USB1
USB2
VGA Video
SD (Secure Digital) slot
Audio

Input Power

The IPC requires:
To connect the DC power supply, refer to "Initial Startup" in chapter 2.
Note:
GFK-2785C
Port Name
1
Shielding is required to be in compliance with the standards identified in Appendix A.
2
Can be permanently connected while the system is running.
3
Intended only for temporary connection.
24VDC, 18–32V range, 48W power supply, Class 2 or LPS
The IPC is supplied with a Phoenix Contact part number
1827716 or 1851245 (spring loaded/quick release) power
terminal block for use with a power supply. The power
supply used must be a UL Listed (or equivalent) Limited
Power Source (LPS) or Class 2 power source.
Power cord
with 28 AWG –16 AWG wires
There are no user-serviceable fuses in the IPC.
Usage
Maximum Cable Length
2
Permanent
3 m (9.8 ft.)
2
Permanent
100 m (328 ft.)
2
Permanent
100 m (328 ft.)
2
Permanent
10 m (32.8 ft.)
3
Maintenance
5 m (16.4 ft.)
3
Maintenance
5 m (16.4 ft.)
2
Permanent
7.6 m (25 ft.)
3
Maintenance
NA
3
Maintenance
2 m (6.5 ft.)
.
PACSystems* RXi Box IPC
Shielding
Required
No
1
Yes
1
Yes
1
Yes
1
Yes
1
Yes
1
Yes
NA
No
FGND 0V +24V
25