FIGURE 5. INTERFACE TWO-WIRE CONVENTIONAL DETECTORS – CLASS B
CONNECT MODULES TO
LISTED COMPATIBLE
HONEYWELL FARENHYT SERIES
CONTROL PANELS ONLY
3.9K EOL
RESISTOR
(INCLUDED)
+
CLASS B IDC (TYPICAL)
POWER TO THE NEXT INTERFACE
MODULE MUST BE EXTERNALLY
SWITCHED TO RESET THE DETECTORS.
AN FRM-1 RELAY CONTROL MODULE CAN BE
USED TO SWITCH POWER FROM A
STANDARD POWER SUPPLY. SEE FIGUR 10.
+
FROM PANEL OR
+
PREVIOUS DEVICE
TO NEXT DEVICE
POWER-LIMITED
SIGNAL LINE CIRCUIT (SLC) 32 VDC MAX.
AND SUPERVISED
SEE PANEL INSTRUCTION MANUAL
FOR WIRE REQUIREMENTS.
FIGURE 6. INTERFACE TWO-WIRE CONVENTIONAL DETECTORS – CLASS A
1.
To select Class A, remove the
two shunts from the "A/B se-
lect" positions.
2.
To use a common power supply
between multiple IDP-Zone-6
modules, connect a long power
supply jumper from T5 or T6
to T5 or T6 on the adjacent
IDP-Zone-6 module.
FIGURE 7. RELAY CONTROL MODULE USED TO DISCONNECT A POWER SUPPLY
TO NEXT
DEVICE
POWER LIMITED DC
POWER SUPPLY,
LISTED FOR FIRE
PROTECTION WITH
BATTERY BACKUP
+
(+)
(–)
DETECTORS MUST BE UL LISTED COMPATIBLE WITH THE MODULE.
INSTALL DETECTORS PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.
CONNECT MODULES TO LISTED COMPATIBLE
HONEYWELL FARENHYT SERIES CONTROL PANELS ONLY
+
+
CLASS A IDC (TYPICAL)
POWER TO THE NEXT INTERFACE
MODULE MUST BE EXTERNALLY
(+)
SWITCHED TO RESET THE DETECTORS.
(–)
AN FRM-1 RELAY CONTROL MODULE CAN BE
USED TO SWITCH POWER FROM A
STANDARD POWER SUPPLY. SEE FIGURE 10.
+
FROM PANEL OR
PREVIOUS DEVICE
+
TO NEXT DEVICE
SIGNAL LINE CIRCUIT (SLC) 32 VDC MAX.
POWER-LIMITED
SEE PANEL INSTRUCTION MANUAL
AND SUPERVISED
FOR WIRE REQUIREMENTS.
RELAY CONTROL
MODULE
BASE ADDRESS
6 7 8 9
6 7 8 9
5
5
10
4
4
11
3
3
12
2
13
2
1
14
1
0
0
15
A/B SELECT
A/B SELECT
DISABLE 1
DISABLE 2
IDC 2
IDC 3
DETECTORS MUST BE UL LISTED COMPATIBLE WITH THE MODULE. INSTALL
DETECTORS PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.
CONNECT MODULES TO LISTED
COMPATIBLE CONTROL PANELS ONLY
3
1.
To use a common power supply
between multiple IDP-Zone-6
modules, connect a long power
supply jumper from T5 or T6
to T5 or T6 on the adjacent
IDP-Zone-6 module.
STATUS
INDICATORS
BASE ADDRESS
6 7 8 9
6 7 8 9
5
5
10
4
4
11
3
3
12
2
13
2
1
14
1
0
0
15
A/B SELECT
A/B SELECT
DISABLE 1
DISABLE 2
FROM PANEL
OR PREVIOUS
DEVICE
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX.
TWISTED PAIR
IS RECOMMENDED
I56-2733-010
C0812-03
STATUS
INDICATORS
C0813-03
C0248-02
7/1/2022