Installation Manual
D
ESCRIPTION
The NCO-10 carbon monoxide (CO) detector is designed for use
with the G-10 CO detection system in car parks and other
enclosed spaces where levels of CO gas must be monitored and
controlled effectively.
The detection system is designed to detect levels of CO lower than
those considered safe for human inhalation and so prevent the
build up of hazardous CO gas. Detection time is less than 10
seconds.
I
NSTALLATION
Placement of carbon monoxide detectors
As CO gas is lighter than air, detectors should be placed just
above the level where the gas is expected to be generated (above
40cm in the case of car parks).
Installing detectors too high or placing detectors too close to
windows, air inlets or other areas of ventilation may prevent the
gas from reaching the detector.
Connection and installation
u
j
Wiring diagram:
Positive line;
v
j
Locking mechanism:
Tab closed (detector head not locked);
k
Tab broken (detector head locked).
The detector is supplied in 3 parts: the detector head, the detector
base and the fixing bracket.
If necessary the fixing bracket can be used as a connection box.
To install:
1. Attach fixing bracket to surface using two 50mm screws.
2. Attach detector base to fixing bracket using two 9mm screws.
3. Insert detector head into base, push and turn clockwise until
detector locks into place.
The detector head may be locked into the base by breaking the
blocking tab at the base of the detector head (figure
remove detector head once the blocking tab has been removed
insert screwdriver into base slot and push.
NOTIFIER ESPAÑA, S.L.
Versión 1-1 / Abril 2004
55317001
k
l
Data;
Negative line.
v
). To
NCO-10 Carbon Monoxide Detector
When in service the detector LED will flash green. A flashing red
LED indicates fault. A constant red LED indicates alarm (this
occurs when CO levels of 50 PPM are detected).
M
AINTENANCE
Fault repair must be carried out by qualified
personnel. Do not manipulate interior.
No specific maintenance is required. The following guidelines will
help ensure your CO detection system remains in good working
order:
§
Exposure to strong gases or fumes may damage sensor.
§
Keep the CO detection system switched on once installed for
the built-in cleaning system to operate.
§
Estimated detector lifespan is four years.
T
C
ECHNICAL
HARACTERISTICS
Input voltage........................................................................9 - 20 VDC
Consumption .............................................................................. 65 mA
Reaction time ..................................................................................10s
Type of sensor ..................................................... TGS semiconductor
Coverage..................................................... up to 300 m² per detector
Maximum number of detectors per zone .........................................15
Service indication .................................................. flashing green LED
Fault indication ...........................................................flashing red LED
Alarm indication........................ constant red LED (CO level 50 PPM)
Dimensions....................................................................81 x Ø109 mm
Protection index ........................................................................... IP 22
Sensor lifespan .........................................................................4 years
Working temperature ............................................................0 to 50
Installation Manual
v
0
C

Advertisement

loading

Summary of Contents for Honeywell Notifier NCO-10

  • Page 1 NCO-10 Carbon Monoxide Detector Installation Manual When in service the detector LED will flash green. A flashing red Installation Manual LED indicates fault. A constant red LED indicates alarm (this occurs when CO levels of 50 PPM are detected). ESCRIPTION AINTENANCE The NCO-10 carbon monoxide (CO) detector is designed for use with the G-10 CO detection system in car parks and other...
  • Page 2 Alcance............hasta 300 m² por detector Nº máximo de detectores por zona..........15 Manual de instalación Indicación de funcionamiento......LED verde intermitente Indicación de fallo ..........LED rojo intermitente ESCRIPCIÓN Indicación de alarma..LED rojo constante (nivel de CO de 50 PPM) El detector de monóxido de carbono (CO) NCO-10 está...
  • Page 3 § Tenere acceso il sistema di rivelazione CO dopo l'installazione ARACTERÍSTICAS ÉCNICAS per consentire il funzionamento del sistema di pulizia Tensão de alimentação............9 -20 V CC incorporato. Consumo ..................65 mA § La durata stimata del rivelatore è di quattro anni. Tempo de reacção .................10 s ARATTERISTICHE TECNICHE Tipo de sensor ............