Hardware Installation

Constant Power

Use constant power for applications that require a constant auxiliary power source. Power is always present at Constant circuits.

Resettable Power

Resettable power is typically used to power beam detectors, flame detectors, and conventional 4-wire smoke detectors. For circuits
selected as Resettable, 24-volt power is always present at the terminals unless a system reset occurs. If a system reset occurs, power is
removed from the terminals for 30 seconds, then re-applied.

Sounder Sync Power

Sounder Sync Power continuously outputs the System Sensor synchronization pattern and is intended for use with B200S sounder bases.

3.6 Conventional Relay Installation

RPS-1000 relay circuits are installed in exactly the same way as FACP main panel relay circuits. For ease of installation, the RPS-1000
output terminals use the same numbering scheme as the FACP terminals. Refer to below listed FACP manual for information on install-
ing conventional relays.
31
Model Number
IFP-2000ECS
IFP-1000ECS
IFP-100ECS
IFP-300ECS
IFP-2100ECS
RPS-1000 / RPS-1000B Manual - P/N 151153:N 08/09/2017
FACP Installation Manual
151430-L8
151460
151458
LS10145-001SK-E
LS10143-001SK-E
Conventional Relay Installation