2: Releasing Operations; Class B Notification Wiring; Class A Notification Wiring - Honeywell Farenhyt RPS-1000 Installation And Operation Manual

Hide thumbs Also See for Farenhyt RPS-1000:
Table of Contents

Advertisement

Flexputs™ I/O Circuits
3.5.2 Releasing Operations
Approved releasing solenoids are list in Table 3.1. Do not mix cross alarming zones with smoke verification zones. There must be at
least two automatic detection devices in each protected space. Spacing must be reduced to 0.7 times the linear spacing in accordance
with NFPA 72.
Manufacturer
Asco

Class B Notification Wiring

You must use an appliance from the list of compatible appliances in the Appendix A.
To install a Class B notification appliance circuit:
1.
Wire Class B Notification appliances as shown in Figure 3.8.
2.
Configure the circuit through programming.

Class A Notification Wiring

You must use an appliance from the list of compatible appliances in the Appendix A at the back of this manual.
To install a Class A notification appliance circuit:
1.
Wire the Class A notification appliances as shown in Figure 3.9.
2.
Configure the circuit for Class A in programming (see the FACP Installation manual).
NOTE: In programming any point that uses multiple I/O circuits are always referred to as the lowest I/O circuit number used. For example,
Figure 3.9 uses both I/O circuit 5 and 6, so in programming it would be referred to as point 5
RPS-1000 / RPS-1000B Manual - P/N 151153:N 08/09/2017
Table 3.1 Approved Releasing Solenoids
Part Number
T8210A107
8210G207
EOL
4.7 k
Figure 3.8 Class B Notification Appliance Circuit Wiring
Figure 3.9 Class A Notification Appliance Circuit Configuration
Rating
Current
24 VDC
3A max
24 VDC
3A max
Notification Wiring
Supervised
Power Limited
Regulated
Regulated
Hardware Installation
Freq
0 Hz
0 Hz
Alarm
Polarity
26