RPS-1000 Board and Terminal Strip Description

2.4 RPS-1000 Board and Terminal Strip Description
Figure 2.1 on page 6 shows the RPS-1000 circuit board including location of terminals, the DIP switch for setting module ID, and the
LED.
Terminal # and Label
1
L
2
G
3
N
4
X
5
O
6
X
7
O
8
X
9
O
RPS-1000 / RPS-1000B Manual - P/N 151153:N 08/09/2017
Figure 2.1 The RPS-1000 Board Layout
Table 2.1 Terminal Strip Description and Electrical Ratings
Description
AC input (hot)
Earth ground
AC input (neutral)
I/O 6*
Flexput™ Circuit
I/O 5*
Flexput™ Circuit
I/O 4*
Flexput™ Circuit
Rating
Voltage
120/240 VAC,
2.7 A
50/60 Hz
1.4 A
N/A
N/A
120/240 VAC,
2.7 A
50/60 Hz
1.4 A
24 VDC
3.0 A Notification Circuits
100 mA Initiation Circuits
24 VDC
3.0 A Notification Circuits
100 mA Initiation Circuits
24 VDC
3.0 A Notification Circuits
100 mA
Initiation Circuits