Honeywell VISTA-250FBPT Installation And Setup Manual page 49

Commercial fire and burglary partitioned security system with scheduling
Hide thumbs Also See for VISTA-250FBPT:
Table of Contents

Advertisement

Using flying leads fr om t er minal block TB4 t o a 9- or 25-pin ser ial connect or .
Plugging t he VT-SERCBL cable int o header J13. This connect or t er minat es in a 9-pin ser ial connect or . To connect t his t o
a PC, you must use a st andard st r aight t hr ough ser ial cable wit h a 9-pin connect or on t he panel end and t he appr opr iat e
connect or for your PC on t he ot her end.
The TB4 met hod is int ended for per manent wir ing, e.g. when connect ing t o WI N-PAK or Pr o-Wat ch. The J13 met hod is
ideal for dir ect -connect pr ogr amming, wher e t he ser ial connect ion being made is only tempor ar y.
When connect ing via TB4, obser ve t he TB4 pin configur at ion shown on t he Summar y of Connect ions label.
When connect ing via J13, use t he VT-SERCBL cable assembly. To connect t his t o a PC, you must use a standar d
st r aight t hr ough ser ial cable wit h a 9-pin connect or on t he panel end and t he appr opr iat e connect or for your PC on t he
ot her end.
I M PORT AN T : When connect ing t he VT-SERCBL cable int o header J13, t he r ed st r ip (pin 1) on t he r ibbon cable should
be t o t he left .
NOTES:
1.
TB4 and J13 cannot be used simultaneously. If you are using one of these connection points to
communicate with the panel, you MUST temporarily disconnect the other wiring.
2.
You cannot use WIN-PAK or Pro-Watch and the Printer at the same time.
Serial Programming Options for Automation Applications
NOTE: You cannot simultaneously use a serial printer and Home/Facility Automation.
The following group of fields must be set to use the serial port for automation applications:
05
Enter 1 to send System Event Messages via RS232 port
14
Enter 1 to enable Home/Facility Automation Control Input
1
78 Extended Home Control Events (Enter 1 for extended)
1 ∗ 79 Home Control Event Types (Enter 1 for each event type to be enabled; 0 to disable)
1 ∗ 80 Enter 1 to improve automation performance by disabling fault/restore messages over the automation
port. If you require live mapping while the system is disarmed, you must enter 0 here.
Panel
9-Pin
TXD
3 (EBI -I PPS)
2 (All Ot her Configur at ions)
RXD
2 (EBI -I PPS)
3 (WI N-PAK or Pr o-Wat ch)
RTS/DTR
8 (WI N-PAK or Pr o-Wat ch)
CTS/DSR
4 (Pr int er Only)
GND
5 (All Configur at ions)
49
25-Pin
2 (EBI -I PPS)
3 (All Ot her Configur at ions)
3 (EBI -I PPS)
2 (WI N-PAK or Pr o-Wat ch)
5 (WI N-PAK or Pr o-Wat ch)
20 (Pr int er Only)
7 (All Configur at ions)