All configurable options for each VistaKey are accomplished via software, firmware, and nonvolatile memory, except
the access point zone number (1-15), which is set via a user-friendly, 16-position rotary switch.
The addition and removal of VistaKey modules from the system is easily accomplished via the VISTA-
128FBPT/VISTA-250FBPT keypad.
Each VistaKey provides one open-collector output trigger (sink 12mA @ 12VDC).
Mounting and Wiring the VistaKey
For detailed instructions on how to install and program the VistaKey, refer the Installation and Setup Guide that
accompanies the VistaKey-SK.
To mount and wire the VistaKey module, perform the following steps:
Step
Action
1
Mount the VistaKey, door strike or mag lock, and card reader.
2
Mount the door status monitor (DSM) and/or request-to-exit (RTE) devices.
3
Using Figure 3-24 as a reference, connect the card reader interface cable to TB3, making the +5V or +12V
connection last.
4
Connect the leads to TB1 in the following order:
a. All ground leads to terminals 2, 5, and 9.
b. The DSM, (optional) RTE, and General Purpose leads to terminals 6, 7, and 8, respectively.
c. Door strike (or mag lock) lead to terminal 10.
d. Local +12V or +24V supply lead to terminal 1.
e. Local +12V or +24V supply lead to the N/C relay terminal 11 (if a mag lock is being used), OR to the N/O
relay terminal 10 (if a door strike is being used).
5
Connect the (–) polling loop and (+) polling loop leads (from the VISTA-128FBPT/VISTA-250FBPT) to
terminals 4 and 3, respectively.
6
Set the Address Select switch to the desired access door number (1-15).
7
Repeat steps 1 through 6 for each VistaKey being installed.
Connecting the Card Reader
Lead from Reader
Green LED
Ground*
DATA 1 (Clock)
DATA 0 (Data)
+5VDC†
+12VDC†
*
TB-3 Terminal 5 is also a ground and may be used instead of terminal 2. Terminals 2 and 5 are a common ground.
Connect to +5VDC OR +12VDC per reader manufacturer's specification.
Lead Color
Orange
Black
White
Green
Red†
Red†
To VistaKey TB3 Terminal #
47
1
2
3
4
6
7