U L
The access control function is not Listed for use in UL Installations.
System Communication
Supports approved ECP Communication Devices that can send Contact ID messages (e.g., Alarmnet GSM, i-
GSM, and Internet communicators)
Supports the 5140DLM optional backup dialer for the second phone line.
Provides supervision of the phone lines (main and backup)
Supports ADEMCO Contact ID; ADEMCO 10-Digit Contact ID and 4+2 Express formats.
The system is shipped defaulted for Contact ID communication. It is the only format capable of uniquely reporting all
250 zones, as well as openings and closings for all 250 users. This requires central stations to be equipped with
receivers that support the complete set of Contact ID report codes, such as the MX8000 or 7810iR-ent. If you need
to update your MX8000 receiver, contact your distributor.
Provides the Dialer Queue Report in the event of a loss of communication between the dialer and the central
station (i.e., telco loss). The total events that will be queued up are 128 (91 Burg + 37 Life Safety). A Dialer
Queue Overflow report (E354) will be sent if the report queue goes beyond its limits. Please note: Life Safety
includes Fire, CO, 24 HR Silent/Audible/Auxiliary alarms, and Duress. Life Safety events may go beyond 37 (up
to 128) if there are no Burg events in the queue. If all dialer attempts are exhausted before communication to
the central station is restored, the queue will be cleared.
Downloading
Supports upload and download capability. (Downloading must be site-initiated for Commercial Fire
installations.)
Can perform unattended downloading (no one at the downloading computer).
Provides an Installer Unattended Program Mode. This allows the installer to program the download phone
number, subscriber number, and primary central station receiver phone number without entering the normal
program mode.
Can periodically and automatically perform a scheduled download.
U L
Remote downloading is not permitted in UL installations. A technician must be on-site in order to test the system
after any system programming is changed.
Event Log
Provides an event log (history log) that can store up to 1000 events (512 for the VISTA-128FBPT).
Can view the event log on an alpha keypad or a graphic touchscreen keypad.
®
V-Plex
Smart Contact Technology
Automatic suppression of fault/restores when disarmed: Smart V-Plex
IS2500SN polling loop motion detectors can be set to stop sending fault/restore signals while the partition is
disarmed. This prevents the polling loop from slowing down due to high bus activity in busy areas. The feature
is enabled by Zone in Zone Programming.
When enabled, within about 5 minutes of program exit, the panel will send the command to the Smart Contacts
to turn off their LED and stop sending faults/restores to the system. (The DT7500SN and IS2500SN will turn off
their LED unless the LED DIP switch is set to ON, in which case the LED will always remain enabled.)
Automatic Test Mode entry: Upon entering Code + 5 (Burglary Walk Test Mode), the panel will again tell the
PIR to enable the LEDs and start sending faults/restores. The LED will remain enabled until the Burglary Walk
Test mode is exited. Removing and replacing the cover of the DT7500SN and IS2500SN, or power-cycling these
sensors will also put them in the walk test mode, enabling the LEDs and sending of faults/restores for 10
minutes.
NOTE: Regardless of Smart Mode, Tamper and Supervision Failures are sent without delay.
PIR Anti-Mask:
panel when the lens has been blocked. For DIP switch settings related to this feature, refer to the motion
detector documentation. Anti-Mask can be enabled in zone programming if a zone type 04 (interior) or 10
(interior with delay) and input type 06 (serial poll) are selected. In the event masking occurs, the message "PIR
masked" will be displayed on the keypad, and a trouble report code is used to report the masking.
Some motion detectors such as the DT7500SN have an "Anti-Mask" feature that will alert the
sensors such as the DT7500SN, and
®