ID50 Series Panel - Operating Manual
Appendix 2 - Maintenance
Create a log book (see Appendix 1) in accordance with
the recommendations of EN54 Part 14. This log book
should be used and maintained for recording events as
described below.
A2.1 Routine Testing
In order to ensure that the system is fully operational,
and to comply with the requirements of EN54 Part 14
and BS 5839 Part 1: 1988, the following routine attention
is recommended:
Daily - Check the panel to ascertain that it indicates
normal operation. If any fault is indicated check that it
has been recorded in the log book and that the appropriate
actions have been taken, e.g. informing the maintaining
company.
Weekly - Test at least one sensor or call point to confirm
the operation of the panel and the audible alarms. Test a
different zone each week and, if possible, a different
device. Keep a record of the device and zone tested each
week. Record and report any malfunction.
Quarterly - The responsible person should ensure that
every three months the system is checked by a competent
person who shall:
Check the log book entries and any action taken.
Check the standby batteries and the charger voltage.
Test at least one device in each zone to check the panel
functions.
Check the operation of the audible alarm and any link to
a remote manned centre, Central Station, etc.
Carry out a visual inspection of the installation to check
for alterations or obstructions and issue a certificate of
testing.
Annually - The responsible person should ensure that,
in addition to the quarterly checks, each device on the
system is tested and that a visual inspection is made of
the cable fittings and equipment.
A2.2 Batteries
As a minimum, replace the batteries every four years.
The battery units should always be disposed of in
accordance with the battery manufacturer 's
recommendations and local regulations.
A2.3 Cleaning
The panel may be cleaned periodically by wiping with a
soft, damp lint-free cloth. Do not use any solvents.