Technical Data
MLS CABLE: 1.5mm unscreened twisted-pair (applicable when detector used as part of a full MLS Digital
Managed Lighting System): see Application Note AN4001
OPERATING VOLTAGE: 230V ~ 50Hz (UK & Europe)
SWITCH CAPACITY: 10 Amps max any lighting load except incandescent lamps: 1500W max (at 230V~)
MAXIMUM RECOMMENDED LOAD (DSI/DALI): 25 Ballasts
MAXIMUM RECOMMENDED MOUNTING HEIGHT: 3.5m
RANGE: Adjustable up to 20m
OFF DELAY: 1 min - 96 hours plus 10-second walk-test mode
PHOTOCELL: Passive/Active/Regulating adjustable 50-5000 lux
MATERIAL: Flame retardant PC/ABS
COLOUR: White RAL9010
WEIGHT: 180g (flush version), 160g (surface version)
IP RATING: 4X
OPERATING TEMPERATURE: 0 C to 40 C
Contact Ex-Or Technical Helpline on 01942 719229 for guidance on installation and commissioning.
Honeywell Ex-Or
Albery House, Springfield Road,
Horsham, West Sussex RH12 2PQ
Tel: + 44 (0)1942 719229
Fax: +44 (0)1942 272767
Email: technicalsales.ex-or@honeywell.com
www.ex-or.com
2
o
o
At the end of their useful life
the packaging and product
should be disposed of via a
suitable recycling centre.
Do not dispose of with normal
household waste.
Do not burn.