Samsung AG010KSV Series Installation Manual page 65

Dvm chiller
Table of Contents

Advertisement

Item
Acid consumption
(pH4.8, mgCaCO
/l)
3
Full hardness
(mgCaCO
/l)
3
Basic item
Calcium hardness
(mgCaCO
/l)
3
Ion-like silica (mgSiO
l)
Iron (mgFe/l)
Copper (mgCu/l)
2-
Sulfide ion (mgS
/l)
Reference
Ammonium ion
item
(mgNH
+
/l)
4
Chlorine residual
(mgCl/l)
Free carbon (mgCO
NOTE
Circle (O) marks in the chart show the factor relevant to corrosion or water scale.
When the water temperature is over 40°C (104°F), steels without protective coating may corrode when expose
to water. Applying corrosion prevention material or degassing can be effective measure to prevent corrosion.
Circulating water and supply water should satisfy the standard shown in the table.
Supplied water or make-up water should be supplied by purified water, neutralized water, tap water except
softened water, and industrial water.
14 items in the table is a typical factor for corrosion and/or water scale.
Chilled water system
Circulation water
(Below 20°C
Supply water
(68°F))
Below 50
Below 50
Below 70
Below 70
Below 50
Below 50
/
2
Below 30
Below 30
Below 1.0
Below 0.3
Below 1.0
Below 0.1
Not detected
Not detected
Below 1.0
Below 0.1
Below 0.3
Below 0.3
/l)
Below 4.0
Below 4.0
2
Heating water system
Low level medium temperature
heating gauge
Circulation water
(Over 20°C (68°F)
Supply water Corrosion
below 60°C (140°F))
Below 50
Below 50
Below 70
Below 70
Below 50
Below 50
Below 30
Below 30
Below 1.0
Below 0.3
Below 1.0
Below 0.1
Not detected
Not detected
Below 0.3
Below 0.1
Below 0.25
Below 0.3
Below 0.4
Below 4.0
Effect
Forming
scale
O
O
O
O
O
O
O
O
O
O
65
English

Hide quick links: