2 Module installation
<Case 1>
Front side
100 (4) or
more
200 (8) or more
<Case 2>
300 (12) or
Height of the wall is unlimited
more
Front side
200 (8) or
more
400 (16) or
more
<Case 3>
100 (4) or
100 (4) or
100 (4) or
more
more
Front side
100 (4) or
100 (4) or
100 (4) or
more
more
Front side
Unit: mm (inch)
100 (4) or
more
100 (4) or
more
400 (16) or
more
100 (4) or
more
more
100 (4) or
more
more
Installing by <Case 1> or <Case 3>
- Height of the wall on the front side should not
be higher than 1500 mm (59 inch).
- Height of the wall on the air inlet side should not
be higher than 500 mm (20 inch).
- Height of the wall on the side is not limited.
- If the height of the wall exceeds by certain value
(h1, h2), additional clearance [(h1)/2, (h2)/2 : Half
of the exceeded distance] should be added to the
service space (S1, S2).
S1+h1/2
Unit: mm (inch)
S2+h2/2
15