Terminal Designations - Honeywell Prestige THX9421R02 Installation Manual

Iaq with equipment interface module

Advertisement

Conventional System
Terminal
Universal relay for humidification,
U1 / U1**
dehumidification, ventilation, or
U2 / U2**
a stage of heating/cooling. U
U3 / U3**
terminals are dry contacts that
require power.
Universal input for a wired indoor
S1 / S1***
sensor, outdoor sensor, discharge
S2 / S2***
sensor, return sensor, dry contact
S3 / S3***
device for alerts or dry contact
S4 / S4***
device for remote setback.
A
Connect to THM4000R1000
B
Wireless Adapter for extended
C
wireless range.
D
** See wiring diagrams on pages 4-5.
*** See wiring diagram below for wiring Dry Contact Devices to display alerts.
Wiring dry contact devices to display alerts
DISCONNECT POWER BEFORE INSTALLATION.
Do not apply power to S1, S2, S3 or S4 terminals.
NOTE:
The dry contact device must
be rated for low voltage.
Connect a dry contact device such as a
water sensor to S1, S2, S3 or S4 terminals.
The thermostat displays an alert when a
problem is detected.
Connecting a stage of heating or cooling to a universal relay
(U1, U2, U3)
1
U1, U2, and U3 are normally
open dry contacts when set up
for a stage of heating or cooling.
2
You must install a field jumper if
the stage of heating or cooling is
powered by the system trans-
former. Do NOT install a field
jumper if the stage of heating has
its own transformer.
69-2739_A.indd 4

Terminal Designations

Description
Heat Pump
Terminal
Universal relay for humidification,
U1 / U1**
dehumidification, ventilation, or
U2 / U2**
a stage of heating/cooling. U
U3 / U3**
terminals are dry contacts that
require power.
Universal input for a wired indoor
S1 / S1***
sensor, outdoor sensor, discharge
S2 / S2***
sensor, return sensor, dry contact
S3 / S3***
device for alerts or dry contact
S4 / S4***
device for remote setback.
A
Connect to THM4000R1000
B
Wireless Adapter for extended
C
wireless range.
D
ONE DRY CONTACT DEVICE
EIM
MULTIPLE DRY CONTACT DEVICES
U3
U3
U2
HEAT STAGE 3,
U2
COOL STAGE 3,
COOL STAGE 4 OR
U1
GEOTHERMAL
1
RADIANT HEAT
U1
2
RH
RC
R
24
VAC
C
4
Description
ON ONE SET OF TERMINALS
TRANSFORMER
24
120
VAC
VAC