Section 3: Primary and Secondary Power for the Audio
Primary power required the for AA-100, and AA-120 Amplifiers are 120 VAC and primary power
required for the AA-100E, and AA-120E are 220/240 VAC. Secondary power (24 VDC battery)
connections must be made at the designated terminals shown in Figure 2.2 and Figure 2.4. Second-
ary power may be obtained from any source of 24 VDC which is Listed for Fire Alarm Signaling
and has sufficient alarm and standby capacity (CHG-120). Use Table 3.1, Table 3.2 and Table 3.3
to calculate amplifier secondary (battery) power requirements.
NOTE: AC POWER MUST BE CONNECTED TO THE SAME CIRCUIT AS THE 7100 SERIES
CONTROL PANEL.
AA-100/AA-100E Primary Amplifiers
AA-120/AA-120E Primary Amplifiers
AA-120/AA-120E Backup Amplifiers
Additional devices powered from the
power supply during a standby
condition
NOTE: The AA-120/AA-120E must be used to back-up the AA-100/AA-100E.
AA-100/AA-100E Primary Amplifiers
AA-120/AA-120E Primary Amplifiers
AA-120/AA-120E Backup Amplifiers
Additional devices powered from the
power supply during a standby
condition
Secondary Current Draw in
Standby (from Table 3.1)
Secondary Current Draw
in Alarm (from Table 3.2)
NOTE: Maximum alarm current from 25AH batteries must not exceed 9A.
Maximum alarm current from 55AH batteries must not exceed 20A.
AA-100/AA-120 Audio Amplifiers Installation/Operation Manual — P/N 9000-0573:C 03/12/2020
Amplifiers
Number of
Device
Devices
[
[
[
[
Total Amplifier Current Draw in
Table 3.1 Secondary Current in Standby
Number of
Device
Devices
[
[
[
[
Total Amplifier Current Draw in Alarm
Table 3.2 Secondary Current in Alarm
[
]
x
[
]
x
Table 3.3 Total Amplifier Secondary Current Draw
Secondary
Current Draw in
Standby
]
x
0.050
]
x
0.050
]
x
0.050
]
x
[
]
Standby
Secondary
Current Draw in
Alarm
]
x
7.3
]
x
7.3
]
x
0.30
]
x
[
]
Required Standby Time
24 or 60 Hours
(Enter 0.25 for 15 minutes)
Standby Current
in Amps
=
=
=
=
=
Standby Current
in Amps
=
=
=
=
=
Battery Requirements
in Amp/Hours
=
=
=