3. In the From zone number enter the zone number beginning the range, and in the To zone
number, enter the zone number ending the range.
4. Tap SELECT SOUNDERS to select the mode of test.
5. The following screen opens for selecting the mode of sounders in zone test.
6. Choose Test with all sounders or Test without sounders option, according to whether you
want to run the test with all sounders or without any sounder. Tap START TEST.
Choose Test with selective sounder option, if you want to run the test with just one sounder
selected from among the onboard and loop sounders.
NS-MN-0032 / 11.2020