Diagnostic Messages For Parameter Errors - Bosch Rexroth R-IB IL 24 PSDO 8-PAC Manual

Table of Contents

Advertisement

DOK-CONTRL-ILPSDO8****-AW04-EN-P
Rexroth Inline Module with Safe Digital Outputs R-IB IL 24 PSDO 8-PAC
Error code
Error cause
dec
hex
64
40
The parameterized F_Destination_Address does not
match the PROFIsafe address set on the safety module (F-
Module).
65
41
Invalid parameterization of F_Destination_Address.
Addresses 0000
66
42
Invalid parameterization of F_Source_Address.
Addresses 0000
67
43
Invalid parameterization of F_WD_Time.
A monitoring time of 0 ms is not permitted.
68
44
Invalid parameterization of F_SIL.
The safety module (F-Module) cannot support the required
SIL.
69
45
Invalid parameterization of F_CRC_Length.
The CRC length generated by the safety module
(F-Module) does not match the required length.
70
46
Invalid F-Parameter record version.
The safety module (F-Module) version does not match the
required version.
71
47
The checksum determined by the safety module
(F-Module) via the PROFIsafe parameters (CRC1) does
not match the CRC1 transmitted in the parameter tele-
gram.
255
FF
During active process data communication, a new
F-Parameter block was received, which differs from the F-
Parameter block currently used.
Incorrect type ID for the F-Parameter block (F_Block_ID).
Table 13-2
F-Parameter parameter errors
Error code
Error cause
(hex)
03F2
iPar_CRC is incorrect
03FA
iPar_CRC is not equal to F_iPar_CRC
03FB
PST_Device_ID is incorrect
03FC
F_Destination_Address in the iParameters is incorrect
03FD
Incorrect order of iParameter blocks
Table 13-3
iParameter parameter errors
13.3

Diagnostic Messages for Parameter Errors

and FFFF
are not permitted.
hex
hex
and FFFF
are not permitted.
hex
hex
Bosch Rexroth AG
Diagnostic Messages for Parameter Errors
Remedy
Make sure that the PROFIsafe address of the
safety module and the value in F_Destina-
tion_Address are the same.
Correct value.
Correct value.
Correct value.
Use a device with the required SIL.
The safety module achieves SIL 3, maximum.
Check device description.
Check device description.
Only V2 mode permitted.
Check F-Parameters, repeat calculation.
Only send modified parameter data when pro-
cess data communication is not active.
Check device description.
Remedy
Check iParameters, repeat calculation.
Apply correct value.
Correct value (20
for
hex
R-IB IL 24 PSDO 8-PAC).
Correct value.
Make sure that the value set under F_Destina-
tion_Address and the value that you have set via
the 10-pos. DIP switch are the same.
Check infrastructure components.
77/94