5: Audio Riser Wiring - Honeywell Fire-Lite Alarms ECC-50DA Installation Manual

Distributed
Table of Contents

Advertisement

Installation
2.1.5 Audio Riser Wiring
The Audio Riser is an analog voice bus that carries the recorded voice messages from the display
board to the ECC-125DAs, or the voice messages generated from a system microphone to the ECC-
125DAs. The maximum resistance on the Audio Riser is 20Ω.
Connect the Audio Riser from TB22 on the main control board to the ECC-125DAs as shown in
Figure 2.6.
ECC-50/125DA Instruction Manual — P/N LS10027-000FL-E:D 5/21/2015
ECC-50/100
main control board
ECC-125DA
ECC-125DA
ECC-125DA
Figure 2.6 ECC-125DA Audio Riser Wiring
firealarmresources.com
ECC-125DA Remote Amplifier
To next
UL-listed 15KΩ
ELR at last panel
on Audio Riser
Supervised,
Power-limited
21