2.1.4 Speaker Wiring
Each ECC-125DA supplies four NAC (Notification Appliance Circuit) for speaker connection. The
speaker circuit can be supervised and wired Class B (Style Y) or Class A (Style Z). Speaker circuit
1 is capable of 100 watts of power at 25 Vrms. Speaker circuit 2-4 are capable of 50 watts (each) at
25 Vrms.

Wiring Lengths

Number Of Speakers
@1/2 W
@1 W
10
5
20
10
30
15
40
20
52
26
80
40
100
50
150
75
200
100
250
125
NOTE: The above table assumes a uniform distribution of the speakers, and that a max of 20%
voltage drop on the last speaker is allowed.

Class B (Style Y)

Figure 2.4 illustrates how to wire speakers to the control panel using Class B (Style Y) supervision.
ECC-50/125DA Instruction Manual — P/N LS10027-000FL-E:D 5/21/2015
Total Load
Vrms
Watts
18 AWG
25Vrms
5W
25Vrms
10W
25Vrms
15W
25Vrms
20W
25Vrms
26W
25Vrms
40W
25Vrms
50W
25Vrms
75W
25Vrms
100W
25Vrms
125W
Table 2.1 Wire Lengths
CIRCUIT 4
CIRCUIT 3
CIRCUIT 2
+
IN
+
OUT
+
IN
+
OUT
+
IN
Supervised,
Power-limited
Figure 2.4 Class B (Style Y) Speaker Configuration
firealarmresources.com
Wire Distance in Feet
16 AWG
14 AWG
3900
6200
2125
3380
1460
2320
1100
1750
760
1200
550
875
450
715
300
476
225
357
180
285
CIRCUIT 1
BATTERY
+
+
OUT
+
IN
+
OUT
ECC-125DA Remote Amplifier
12 AWG
9860
15680
5375
8540
3690
5870
2780
4420
1920
3050
1390
2200
1130
1800
753
1200
565
900
452
720
UL-Listed
15K Ω ELR
19