Honeywell Notifier DSE1-PW Installation Manual page 3

Sounder with remote power supply

Advertisement

ON 
OFF 
CHART 2 
DIP 
Function 
DIP1 
Alarm timing 
DIP2 
Alarm timing 
DIP3 
Flash control 
DIP4 
LED mode 
DIP5 
Sound pattern selection 
DIP6 
Power set‐up 
DIP7 
Power set‐up 
DIP8 
OFF – Do not modify 
CHART 4: FLASHING SELECTION 
DIP 3 
OFF 
FLASH CONTROLLED BY ALARM INPUTS 
ON 
FLASH CONTROLLED BY M9 TEST INPUT 
 
CHART 6: AVERAGE CURRENT SELECTION ONLY SOUND [Average (Peak) mA]. With FLASHING add 80mA to the value on the chart 
 
 
AVERAGE 
DIP 6  DIP 7 
CONSUMPTION 
OFF 
OFF 
100mA 
ON 
OFF 
200mA 
OFF 
ON 
400mA 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
DIP‐SWITCH SETTING and TERMINALS
FLASH CONTROL 
DIP 5 OFF 
S1 
DIN33 
NFS32 
Falling 
dual tone 
(500‐1150Hz) 
(440‐554Hz) 
60 (110 peak) 
95 (95 peak) 
120 (180 peak) 
150 (160 peak) 130 (210 peak)
250 (350 peak) 
330 (370 peak) 250 (425 peak)
CHART 1 
Terminals 
+ S1/RC (1) 
‐ S1/RC (2) 
+S2 (3) 
R (4) 
‐S2 R (5) 
+ S3 (6) 
‐ S3 (7) 
ANM (8) 
TEST (9) 
CHART 3: SOUNDER TIMING 
DIP 1 DIP 2
OFF 
OFF 
ON 
OFF 
OFF 
ON 
ON 
ON 
CHART 5: LED FLASHING UNIT 
DIP4 
OFF 
ON 
 
S2
S3
ISO8021 ‐ 3 
pulses + pause
(515Hz) 
60 (100 peak) 
Connections 
Sound control 1: 24V =  sound, 0V = silent 
Sound control 1: 0V =  sound, 24V = silent 
Sound control 2: 24V =  sound, 0V = silent 
Not Connected. Free to use 
Sound control 2: 0V =  sound, 24V = silent 
Sound control 3: 24V =  sound, 0V = silent 
Sound control 3: 0V =  sound, 24V = silent 
Syncronism 
LED Control see DIP 3 
ALARM TIMING 
INFINITE (BY DEFAULT, COMPLYING TO EN54‐3) 
3 MINUTES (NOT COMPLYING TO EN54‐3) 
(8 MINUTES (NOT COMPLYING TO EN54‐3) 
15 MINUTES (NOT COMPLYING TO EN54‐3) 
LEDs MODE 
STEADY ON 
FLASHING 
DIP 5 ON 
S1
S2 
BS5839 
NEN2575 
Dual Tone 
rising + pause 
(500‐1000Hz) 
(500‐1200Hz) 
70 (100 peak) 
70 (100 peak) 
200 (255 peak) 160 (285 peak)  180 (180 peak)
370 (470 peak) 290 (520 peak)  325 (350 peak)
S3
Continuous 
(625Hz) 
85 (90 peak) 