Duct mounting kit

Advertisement

Sensepoint Plus, Sensepoint Pro, Series 3000 XPIS and Sensepoint XCD Duct Mounting Kit
Assembling Duct Components
1
Drill a 100 mm diameter hole in the target duct wall.
2
Drill 4 x 10 mm equidistant holes around it. (use the part-duct as a template).
3
Align the Gasket over the holes.
Refer to the following diagram for the component positioning.
4
Fit the Gasket Retaining Plate over the gasket.
5
Fit the four Plate Fixings through the duct wall from the inside.
The hexagon shaped step on the fixings align with the hexagon shaped holes in the
retaining plate.
6
Secure the plate to the fixings using the knurled nuts.