Connecting DCS with Fire Alarm Control Panel through LPI-ModBus

LPI-ModBus(Loop Peripherals Interface) is a SLC-ModBus converter. X-618 is compatible with the
V2.0 and V3.0 version of the LPI-ModBus module. The Converter provides a communication link
between FAS and the third party system that use the modbus/RTU communication protocol. Each
module supports max 6 DCS, 48 zones. The module power will be provided by the fire alarm
control panel. Please refer <LPI-ModBus converter User's Manual > to get more detail.
LPI-ModBus is master, DCS is slave, and the slave address can be set in the Config software. It is
necessary that DCS, LPI-ModBus and FAS must be set respectively before working.
Figure 26 Schematic Diagram of Connecting DCS with Fire Alarm Control Panel through LPI-ModBus

Connecting NRI with the Fire Alarm Control Panel through LPI-ModBus

If NRI is connected with the fire alarm control panel through the LPI-ModBus module, this
communication mode can achieve the fire alarm linkage between 32 DCS at most. In this
communication mode, NRI is master, LPI-ModBus module is slave; NRI supports up to 6 LPI-
ModBus module. The RS-485 interface of LPI-ModBus module will be linked with NRI's RS-485
interface (A1/B1) directly. If need to connect with multiple LPI-ModBus modules, RS-485 bus wiring
need to comply with the relevant standards, such as not star connection, ensure the
communication quality. The schematic diagram of connecting NRI with the fire alarm control panel
through LPI-ModBus module is shown as below.