Pegasus High Temperature Controller Shortform
ZA0937-ZBC Issue E
Overview
Pegasus (Figure 2) is a refrigeration controller
used to switch refrigeration ON, if the operating
o
temperature
(4
C)
temperature setting, and OFF if the operating
temperature falls below the running temperature
o
setting by 3
C. Four bit switches located on the
controller board control the frequency defrost. A
display (Figure 1), connected to the controller can
show either the operating temperature or one of
the following four messages:
1.
dF: the controller is in defrost
2.
Flashing
between
temperature: controller is recovering from
defrost
3.
Flashing between PF1 and 30
4.
Flashing
between
temperature: over temperature alarm
The maximum defrost time is set by adjusting
RV4 and viewed whilst in the setting mode. Table
1 below, describes these settings:
Channel
Reading
ID
Pr
Case
temperature
probe
Ch4
Maximum
defrost
time
Table 1: Pegasus Control Settings
Defrost Settings
The controller initiates defrosts at intervals set on
the defrost frequency switches (Table 2).
The compressor is held OFF for the maximum
defrost period, during defrost.
After defrost the controller enters the recovery
state. The compressor is cycled as normal for 15
minutes. During recovery the display flashes
between the operating temperature and "dF".
Setting Mode
Setting mode is selected using the channel setting
push button (or an optional remote channel select
button) on the controller board. Hold down the
button to view the termination time (Ch4) on the
display (Table 1). Release the button to see the
value appropriate to that channel. Adjust the
setting using a screwdriver whilst the appropriate
Honeywell Refrigeration Control, Newhouse Industrial Estate, Motherwell, ML1 5SB.
Tel: 01698 481698, Fax: 01698 481699, Web:
May18, 2007.
exceeds
the
running
dF
and
operating
o
C: probe failure
AL
and
operating
Pot
Range
o
-30
C to
o
+30
C
RV4
10 to 40
minutes
channel is selected. The display automatically
reverts to normal after a period of 30 seconds.
Probes
Pegasus is equipped with two inputs; P1 and
AUX. The case temperature probe connects to P1
and the manual defrost initiation switch to AUX.
Power Up
The fans are powered continuously from a supply
on the board. The compressor is held OFF for two
minutes after power up.
Hold down the channel select button whilst the
case is switched on to override the two minute
delay period and start the compressor immediately
on power up.
Case Test Mode
Put the controller into test mode by connecting the
link on LK2 (Figure 2). Bit switch 3 now controls
the relay output. The display shows bC followed
by the software version.
Over Temperature Alarm
The over temperature alarm level is set at 10
with a 30 minute alarm delay. The over
temperature alarm level and the alarm delay
cannot be altered. The over temperature alarm is
disabled during defrost.
Compressor Minimum On/Off Time
The minimum ON/OFF time ensures that when
the compressor switches ON/OFF, it remains
ON/OFF, for a minimum period of two minutes.
Probe Fault
If a probe fault occurs on P1, the display flashes
between PF1 and 30
ON and then OFF continuously , every 8 minutes.
Connecting a Display
Connect the display to your Pegasus controller
using the inf ormation shown in Figures 1 and 2.
Figure 1: Connecting a Display
www.refrigeration.europe.honeywell.com
o
C. The compressor switches
o
C

Advertisement

loading

Summary of Contents for Honeywell Pegasus 190937-ZBC

  • Page 1 (Table 1). Release the button to see the value appropriate to that channel. Adjust the Figure 1: Connecting a Display setting using a screwdriver whilst the appropriate Honeywell Refrigeration Control, Newhouse Industrial Estate, Motherwell, ML1 5SB. Tel: 01698 481698, Fax: 01698 481699, Web: www.refrigeration.europe.honeywell.com...