Calibration Handbook
The second line shows the current gas detector type: Short Range 5 - 40m (15 - 130ft), Medium
Range 20 - 120m (65 - 390ft) or Long Range 20 - 200m (65 - 650ft)
6. Press
, the Current Path Length in meters is displayed. Verify actual path distance (in meters)
between transmitter and receiver.
Minimum and maximum path length entry options for each gas detector are:
Gas Detector Type Minimum Range Maximum Range Step Size
Short Range
Medium Range
Long Range
7. When finished press Enter. Self-test routine is started display shows following message:
When test is successful following message is displayed:
The screen then changes to show a display similar to the following.
The first line of the display shows the magnitude of the current signal level as a horizontal bar graph - SIG:
The second line of the display shows the magnitude of the current target signal level as a horizontal bar
graph - TGT:
NOTE
a) The overall objective of alignment is to maximize the SIG level. Maximized SIG corresponds to optimal
alignment.
b) 4HE )NSTRUMENT !SSISTED !LIGNMENT )!! SYSTEM ONLY ALLOWS %XCEL TO BE INITIALIZED IF THE 3)' LEVEL IS
GREATER THAN OR EQUAL TO THE 4'4 LEVEL WHEN %NTER IS PRESSED
c) 4HE SMALLEST 4'4 SIGNAL LEVEL THAT IS INITIALLY SET WILL BE EQUIVALENT TO
for the installation's path length.
d) 4HE 4'4 LEVEL WILL INCREASE GRADUALLY IF THE CURRENT 3)' LEVEL IS LARGER THAN THE 4'4 LEVEL
4HE 4'4 SIGNAL LEVEL ONLY EVER INCREASES )F THE CURRENT 3)' LEVEL FALLS BELOW THE 4'4 LEVEL 4'4 WILL
remain at its previous highest value. In order to initialize the gas detector the SIG level must be brought
back above the TGT level.
Calibrate
Install
System Type
Shrt Range
Path Length
23
4m / 16ft
40m / 131ft
20m / 66ft
120m / 394ft
20m / 66ft
200m / 656ft
Self Test
Please Wait
Checks Passed
SIG:
TGT:
80
1m / 3ft
1m / 3ft
1m / 3ft
OF THE SIGNAL EXPECTED
Searchline Excel