301W Calibration Procedure - Honeywell VA201T Calibration Handbook

Fixed gas detection
Table of Contents

Advertisement

301W Calibration Procedure

1. Warm-Up Period
Turn the unit on for a minimum of fifteen (15) minutes.
2. Connecting the Hardware
Screw the regulator to the appropriate calibration gas cylinder.
Adjust the regulator with a flow rate of according to specification
Gas
CO
NO
O
2
Connect the regulator outlet to the sensor as shown.
3. Remote Calibrating the 301W Sensor
When using the 301W in a network of sensors, connected to a 301C controller (with firmware 3.0 or higher),
it is possible to perform a "remote calibration" using the 301C menu:
1. Using the navigation arrows, access the 301C's menu
2. Scroll through the menu options and select option 7. Network
3. Scroll through the Network options screens to the last screen and select the Calibration option
The Calibration screen contains four (4) lines of information:
Line 1: Indicates the mode (Calib, meaning calibration), the (Modbus) address of the device to calibrate
(121) and the type of device to calibrate (301W)
Line 2: Indicates the status (Normal or In calib...) of the specified device
Line 3: Displays the function to perform (Set Zero)
VA301W Wireless Transmitter
301W CALIBRATION INFORMATION
Scale
Warm-up Flow Rate
0 - 255 ppm
15 min
0 – 10.2 ppm
15 min
2
0 – 25.5 % Vol.
15 min
Calib
Status:
Set Zero
Set Span
Calibration Handbook
0.5L/min
1L/min
0.5L/min
121
301W
In calib...
246
PPM
33
Notes