Vigilon BACnet Gateway
Connect the BACnet Gateway to a switch/hub.
a.
Change the IP address of the network adaptor on you PC to be the same as the Gateway Routing IP
b.
address (10.1.6.2).
Launch the GENT Configuration tool and make the necessary changes to the GENTGW.ini file.
c.
j
Select the required time zone country / location.
k
Enter the require BBMD IP address and subnet mask to which BACnet Gateway registers as
a foreign device in the same LAN to which the board is connected.
l
These default values set for event priorities are suitable for most applications.
m
If necessary enter the required Gateway IP configuration values to site specific requirements.
The values shown are those set during initialisation.
n
Enter the business name in Gateway location.
o
Save the settings made to GENTGW.ini file.
"
The Network number and Gateway ID has to be different if two Gateways are using the same BACnet client and subnet.
d.
Save the changes made to the configuration.
Set the IP address of the BACnet Gateway in the Destination IP and then Upload the configuration.
e.
File
Ensure the file GENTGW.ini file is in the same path and resides in the same directory as
f.
Configurator.exe.
Restart the BACnet Gateway to ensure the configuration changes are effective.
g.
Reconfigure the network adaptor as required.
h.