SYSTEM SPECIFICATIONS
System Capacity
• Intelligent Digital Communication Loops ....................................1
• Addressable device capacity ....................................................50
• Programmable software zones .................................................50
• Annunciators.............................................................................16
Electrical Specifications
AC Power: Operates in either 120 or 240 VAC, 50/60 Hz, 1.75 A,
auto-sensing-no switch required. Wire size: minimum 14 AWG (2.00
mm2) with 600 V insulation. Nonpower-limited, super-vised.
Battery: Two 12 V 18 AH lead-acid batteries. Battery Charger
Capacity: 7-18 AH (EX-50XC cabinet holds maximum of two 18 AH
batteries.)
Digital Communication Loop: Supervised and power-limited.
Notification Appliance Circuits: Terminal Block provides connec-
tions for two NACs, Style Y (Class B) or Style Z (Class A). Special
Application power. Power-limited, supervised circuitry. Maximum sig-
naling current per circuit: 2.5 amps special application, 250mA regu-
lated. End-of-Line Resistor: 4.7k ohm, ½ watt (P/N 71252 UL listed)
for Style Y (Class B) NAC; system capable of 1.9 kΩ - 22 kΩ ELR
range. Refer to the Fire•Lite Device Compatibility Document for
listed compatible devices.
Two Programmable Relays and One Fixed Trouble Relay: Con-
tact rating: 2.0 A @ 30 VDC (resistive), 0.5 A @ 30 VAC (resistive).
Form-C relays, non-power-limited, non-supervised.
This document is not intended to be used for
installation purposes. We try to keep our product
information up-to-date and accurate. We cannot
cover all specific applications or anticipate all
requirements. All specifications are subject to
Page 4 of 4 — Canadian DF-60954:C • 7/16/2018
change without notice.
Cabinet Specifications
Door: 19.26" (48.92 cm.) high x 16.82" (42.73 cm.) wide x 0.72"
(1.82 cm.) deep. Backbox: 19.00" (48.26 cm.) high x 16.65" (42.29
cm.) wide x 5.25" (13.34 cm.) deep. Trim Ring (TR-CE): 22.00"
(55.88 cm.) high x 19.65" (49.91 cm.) wide.
Shipping Specifications
Weight: 26.9 lbs. (12.20 kg.) Dimensions: 20.00" (50.80 cm.) high
x 22.5" (57.15 cm.) wide x 8.5" (21.59 cm.) deep.
Temperature and Humidity Ranges
This system meets requirements for operation at 0 – 49°C and at a
relative humidity 93% ± 2% RH (non-condensing) at 32°C ± 2°C.
However, the useful life of the system's standby batteries and the
electronic components may be adversely affected by extreme tem-
perature ranges and humidity. Therefore, it is recommended that this
system and its peripherals be installed in an environment with a nor-
mal room temperature of 15 – 27°C.
Agency Listings and Approvals
The listings and approvals below apply to the basic ES-50XC control
panel. In some cases, certain modules may not be listed by certain
approval agencies, or listing may be in process. Consult factory for
latest listing status.
• ULC: S624
LiteSpeed™ is a trademark and Fire-Lite® Alarms and System Sensor® are
registered trademarks of Honeywell International Inc. Microsoft® and Windows® are
registered trademarks of the Microsoft Corporation.
©2018 by Honeywell International Inc. All rights reserved. Unauthorized use of this
document is strictly prohibited.
For more information, contact Fire•Lite Alarms.
(888) 289-1114
10 Whitmore Road
Woodbridge, Ontario LZL 7Z4
www.firelite.com

Advertisement

loading