• Continuous fire protection during online programming
• Program Check automatically catches common errors not linked
to any zone or input point
• OFFLINE PROGRAMMING: Create the entire program in your
office using FS-Tools, a Windows®-based software package, and
upload/download system programming locally. Offline program-
ming requires an ethernet connection. FS-Tools is available on
www.firelite.com.
User interface
LED INDICATORS
• Fire Alarm (red)
• AC Power (green)
• Supervisory (yellow)
• Trouble (yellow)
• Ground fault (yellow)
• Battery fault (yellow)
• Disabled (yellow)
• Maintenance (yellow)
• Communication (yellow)
• Alarm Silenced (yellow)
• F1-F4 Function Keys (yellow)
KEYPAD
• 16 key alpha-numeric pad
• Acknowledge
• Alarm Silence
• Drill (Manual Evacuate)
• Reset (lamp test)
• Four (4) programmable function keys
Product Line Information
ES-50XC: Addressable Fire Alarm Control Panel with one DCL loop.
Includes main circuit board with display, pre-installed communicator,
chassis with transformer, dress panel, backbox with door, plastic bag
containing screws, cables, key, etc., manual.
FS-Tools: Programming software for Windows®-based PC com-
puter. Available for download at www.firelite.com.
CELL-CAB-FLC/CELL-MODC: Optional GSM communicators.
TR-CE: Optional trim ring for semi-flush mounting.
BB-2F: Optional cabinet for one or two modules.
BB-6F: Optional cabinet for up to six modules mounted on CHS-6
chassis.
BB-26: Battery backbox, holds up to two 25 AH batteries and CHG-
75.
BB-55F: Battery box, houses two 55 AH batteries
CHS-6: Chassis, mounts up to six multi-modules in a BB-6F cabinet.
CHG-75: Battery charger for lead-acid batteries with a rating of 25 to
75 AH.
CHG-120F: Remote battery charging system for lead-acid batteries
with a rating of 55 to 120 AH. Requires additional BB-55F for mount-
ing.
BAT Series: Batteries, see data sheet DF-52397.
PRN Series: ULC listed compatible event printer. Uses tractor-fed
paper.
OPTIONAL MODULES
4XTMF Reverse Polarity Transmitter Module: Provides a super-
vised output for local energy municipal box transmitter, alarm and
trouble. Includes a disable switch and disable trouble LED
COMPATIBLE ANNUNCIATORS
ANN-100: Remote LCD annunciator mimics the information dis-
played on the FACP LCD display. Recommended wire type is un-
shielded.
Page 2 of 4 — Canadian DF-60954:C • 7/16/2018
ANN-I/O: LED Driver Module provides connections to a user sup-
plied graphic annunciator. (See DF-52430.)
ANN-LED: Annunciator Module provides three LEDs for each zone:
Alarm, Trouble, and Supervisory. Ships with red enclosure. (See
DF-60241.)
ANN-RLED: Provides alarm (red) indicators for up to 30 input zones
or addressable points. (See DF-60241.)
ANN-RLY: Relay Module provides 10 programmable Form-C relays.
Can be mounted inside the cabinet. (See DF-52431.)
ANN-S/PG: Serial/Parallel Printer Gateway module provides a con-
nection for a serial or parallel printer. (See DF-52429.)
ADDRESSABLE DEVICES
All feature a polling LED and rotary switches for addressing.
SD365A: Addressable low-profile photoelectric smoke detector. Lite-
Speed only.
SD365A-IV: Addressable low-profile photoelectric smoke detector.
Ivory. LiteSpeed and CLIP mode.
SD365TA: Addressable low-profile photoelectric smoke detector
with thermal sensor. LiteSpeed only.
SD365TA-IV: Addressable low-profile photoelectric smoke detector
with thermal sensor. Ivory. LiteSpeed and CLIP mode.
SD365RA: Remote test capable addressable photoelectric smoke
detector for use with DNRA duct detector housing. LiteSpeed only.
SD365RA-IV: Remote test capable addressable photoelectric
smoke detector for use with DNRA duct detector housing. Ivory. Lite-
Speed and CLIP mode.
H365A: Low-profile 135°F fixed thermal sensor. LiteSpeed only.
H365A-IV: Low-profile 135°F fixed thermal sensor. Ivory. LiteSpeed
and CLIP mode.
H365RA: Low-profile, intelligent, rate-of-rise thermal sensor. Lite-
Speed only.
H365RA-IV: Low-profile, intelligent, rate-of-rise thermal sensor.
Ivory. LiteSpeed and CLIP mode.
H365HTA: Low-profile intelligent 190°F/88°C fixed thermal sensor.
LiteSpeed only.
H365HTA-IV: Low-profile intelligent 190°F/88°C fixed thermal sen-
sor. Ivory. LiteSpeed and CLIP mode.
Legacy Devices
CP355A: Addressable low-profile ionization smoke detector.
SD355A/SD365A: Addressable low-profile photoelectric smoke
detector.
SD355TA/SD365TA: Addressable low-profile photoelectric smoke
detector with thermal sensor.
SD355RA/SD365RA: Remote test capable addressable photoelec-
tric smoke detector for use with DNRA duct detector housing.
H355A/H365A: Fast-response, low-profile heat detector.
H355RA/H365RA: Fast-response, low-profile heat detector with
rate-of-rise option.
H355HTA/H365HTA: Fast-response, low-profile heat detector that
activates at 190°F/88°C.
AD355A: Low-profile, intelligent, "Adapt" multi-sensor detector
(B350LP base included).
B200SA: Programmable, addressable sounder base.
B200SRA: Addressable sounder base.
BEAM355A: Intelligent beam smoke detector.
BEAM355SA: Intelligent beam smoke detector with integral sensitiv-
.
ity test.
D355PLA: InnovairFlex low-flow non-relay duct-detector housing;
includes SD355RA/SD365RA.
DNRA: InnovairFlex low-flow non-relay duct-detector housing.(Order
SD355RA/SD365RA separately.)