Honeywell Fire-Lite Alarms MS-9200 Wiring Manual page 29

Intelligent control panel, slc
Table of Contents

Advertisement

Descriptions
MMF-300-10 Monitor Module
This is an addressable monitor module intended to interface between the FACP and up to ten (10) Class B or five (5) Class A IDCs con-
taining normally open contact devices.
This type of module is contained in either a BB-2 or BB-6 cabinet. The BB-2 can accommodate up to 2 modules and the BB-6, which
requires the CH-6 chassis, can accommodate up to 6 modules.
See the Installation Instructions provided with module for proper installation into a cabinet.
Disable Address
Place shunt in:
Disable 1 position to disable highest module address
Disable 2 position to disable highest two module addresses
FireLite SLC Wiring Manual — P/N 51309:R3 7/29/2019
Class B or Class A Select
Remove shunt for Class A circuits
Figure 5.2 MMF-300-10 Monitor Module
Monitor Modules
SLC Address
Set rotary switches to base
(first) address of modules
29