Download Print this page

Honeywell AirScan iR Instruction Manual page 9

Refrigerant sensor for industrial applications

Advertisement

3
Operation
LED Indicators and Blink Sequence
Figure 6. LED Blink Sequence
SEQUENCE
1 sec. 2 sec. 3 sec.
SOURCE BLINK
SLOW BLINK
MEDIUM DOUBLE BLINK
FAST BLINK
CONTINUOUS ON
Green Power LED
Continuous ON when power is applied
Yellow System LED
Continuous ON during normal filtered output run
mode — "dead band" from 4 to 4.6 mA
Slow blink during normal non-filtered output run
mode
Fast blink indicating unit lost calibration data
OFF during 4/20 mA loop check
Yellow Calibrate LED
Continuous momentary ON for auto-zero mode
activation
Slow blink for 4 mA output calibration mode
Medium double blink indicates 4/20 mA loop
check .5 mA (low)
Fast blink for "span" calibration mode and
4/20 mA loop check 22 mA (high)
Manning AirScan-iR Refrigerant Sensor
continued
19100 AirScan-iR-ind 05/2006 REVA Copyright © 2006 Manning Systems, Inc. All Rights Reserved.
Red Fault LED (all scenarios produce a .5 mA
output)
Continuous ON indicates a failed source, low
signal, or circuit failure
Slow blink indicates the power supply DC 24V
input voltage is too low.
Medium double blink indicates sensor is outside
the operating temperature range.
Fast blink indicates the signal drifted below
4 mA and needs to be re-calibrated, only in non-
filtered output run mode (no dead-band).
Red mA Fault LED attempts to output .5 mA
fault signal
Fast blink indicates 4/20 mA loop failure or load
resistance too high
Green Source LED
One blink every 2 seconds indicates when
source is energized and also that the source is
not short circuited.
Green ATMOS LED
Continuous ON indicates ATMOS circuitry is
active or adjusting the enclosure's internal
environmental conditions for the sensor to
function reliably.
NOTES:
If the Source LED isn't blinking, do not proceed
until the condition is corrected.
If a Fault LED is lighted, immediately refer to
Fault Indicator Error Sequences (page 11) to
determine potential problem. Do not attempt
calibration if a Fault is indicated.
All status LED's are subordinate to Fault
indicators.
If an LED is indicated as OFF, it must actually
be OFF for proper sensor operation.
If an LED status is N/A (not applicable), that
LED indication may vary depending on other
operational factors.
9

Advertisement

loading