Schedule
Maintenance Mode
1 Setting
■ When there is a computer to operate the Schedule function, it is not possible to operate from another computer.
■ It is possible to manage or proceed from each Group.
■ There are 16 Schedule items that can be registered for each day of the week and any specific day.
■ Registration is possible according to three seasons: [Standard Season], [Summer Season] and [Winter Season].
■ The Operation Pattern includes ON/OFF, Operation Mode, Setting Temperature, Fan speed, Louver, RC
operation, Outdoor Capacity Control, Lower Noise items.
■ The Operation Pattern name and content can be modified.
■ The Specific day 1 to 5 is registrable until December 31st of the following year.
■ The Schedule register consists of : All, Block and Group as follows.
■ The Schedule function will operate when the time elapsed. In such case, it is possible that the power of the air
conditioning unit is turned OFF. Then, even turned ON, the Schedule content may not match.
■ The content set will be expanded from the upper level to the lower level (All, Block, Group).
■ When [Overwrite All] is selected in Setting Method, the content set from upper level will copy all the setting
content from the Upper level to the lower level (All - Block - Group). Also, when [Overwrite only where changed]
is selected, the modified location only will be specified and the setting content from the upper level to the lower
level will be copied.
● Outdoor Unit Setting
To proceed with the Capacity control in [Schedule] [External input], select the desired Outdoor unit in [Settings] then
[Outdoor unit] and check [Capacity].
[Outdoor unit Capacity] is a function to save by the closest designated percent the Power consumption regarding the
cooling rated power amount.
The setting will be applied within 15 minutes after being set.
Even if the Capacity control is proceeded at 0%, the Power consumption will not be 0 because the Standby Power* is
generated.
If the Outdoor unit is in Startup Control or during defrosting, it will be excluded from this Control.
This Control does not ensure the Power consumption as in the setting.
* The Standby Power is a Power amount that is used to prepare for the next operation when the Air Conditioner is stopped.
When performing Lower Noise in [Schedule] [External input], select the desired Outdoor unit in [Settings] [Outdoor unit]
and check [Capacity] then [Lower noise].
If the Outdoor unit which does not support [Lower noise] function is set by [Lower noise], be careful because the
[Capacity] function may not operate correctly.
When the option for [Low noise] is applied simultaneously with the option for [Capacity], only the [Low noise] option will
operate correctly.
P5416904
Management Mode
Block
Group
Group
Unit
Unit
Standard Season
Summer Season
Mon.
Mon.
Sun.
Sun.
Spec. day 1
Spec. day 1
Spec. day 5
Spec. day 5
Control Mode
Block
Group
Unit
It is possible to set the
Winter Season
Schedule in 3 seasons
Mon.
(Standard season - Summer
season - Winter season) in
Sun.
each Group.
Spec. day 1
It is possible to set the
specific day for 5 days in
each season.
Spec. day 5
Upper
All
Block
Lower
Group
Unit