TAMPER RESISTANCE
Intelligent programmable temperature sensors include a tamper-resistant ca-
pability that prevents their removal from the base without the use of a tool.
Refer to the base manual for details on making use of this capability.
TESTING
Before testing, notify the proper authorities that the system is undergoing
maintenance, and will temporarily be out of service. Disable the system to
prevent unwanted alarms.
All sensors must be tested after installation and periodically thereafter. Test-
ing methods must satisfy the Authority Having Jurisdiction (AHJ). Sensors
offer maximum performance when tested and maintained in compliance with
NFPA 72.
A.
Test Magnet (Model No. M02-04 - optional)
1. Place the optional test magnet against the cover in the magnet test
area, as shown in Figure 3, to activate the test feature.
2. The LEDs should latch on within 10 seconds, indicating alarm and
annunciating the panel.
3. Reset the detector at the system control panel.
B.
Direct Heat Method (Hair dryer of 1000 – 1500 watts)
1. From the side of the detector, direct the heat toward the sensor. Hold
the heat source about 6 inches (15 cm) away to prevent damage to
the cover during testing.
2. The LEDs on the detector should light when the temperature at the
detector reaches the alarm setpoint. If the LEDs fail to light, check the
power to the detector and the wiring in the detector base.
3. Reset the detector at the system control panel.
Detectors that fail these tests may need to be cleaned as described under
CLEANING and retested.
CLEANING
Before removing the detector, notify the proper authorities that the smoke
detector system is undergoing maintenance and will be temporarily out of
service.
Disable the zone or system undergoing maintenance to prevent unwanted
alarms.
1.
Remove the sensor to be cleaned from the system.
2.
Use a vacuum cleaner or compressed air to remove dust and debris from
the sensing area.
3.
Reinstall the detector.
4.
Test the detector as described in TESTING.
5.
Reconnect disabled circuits.
6.
Notify the proper authorities that the system is back on line.
FM CLASSIFICATION
RTI ratings are for installations which must comply with FM 3210.
135°F Fixed RTI:
Rate of Rise/135°F Fixed RTI:
190°F Fixed RTI:
Please refer to insert for the Limitations of Fire Alarm Systems
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must
accept any interference received, including interference that may cause undesired operation.
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used
in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installa-
tion. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try
to correct the interference by one or more of the following measures:
– Reorient or relocate the receiving antenna.
– Increase the separation between the equipment and receiver.
– Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
– Consult the dealer or an experienced radio/TV technician for help.
Honeywell
®
and Farenhyt
®
are registered trademarks of Honeywell International, Inc.
FAST
V2-FAST
QUICK
FCC STATEMENT
FIGURE 3: FEATURES OF THE HEAT DETECTOR
Magnet
Test
Marker
Base
Alignment
Notch
LED
FIGURE 4: CLEANING THE HEAT DETECTOR
Thermistor
2
Base Alignment Notch
Magnet
Test
Marker
LED
C2025-00
}
Access to
Sensing Area
C2026-00
I56-6533-000
©2017 Honeywell. 11/15/2017

Advertisement

loading

This manual is also suitable for:

Idp-heat-wIdp-heat-ivIdp-heat-ror-wIdp-heat-ror-ivIdp-heat-ht-wIdp-heat-ht-iv