Relay not Responding

This fault is raised when the ECU double knock relay does not switch when required. The relay is
mapped as an output that is activated by a triggered input.

Indications

Fault buzzer sounds.
Display scrolls between two events, one showing the addressable relay device that has not
switched, the other showing the event that has triggered it (usually a fire event). For example:
FIRE
Zone 001 Dev 001
Second Floor, Laundry Room
RELAY FAULT
Zone 001 Dev 086
Events are printed (if printer configured).
Zone in which the relay fault occurred is indicated by the appropriate red Zone LED.

Possible Causes

ECU double knock relay is in an isolated state.
ECU double knock relay is faulty.

Corrective Actions

1. Press the ACCEPT button to accept the fault.
2. If the yellow Isolated LED is on, check whether the relay is isolated. If the relay is isolated then
investigate the reasons for this. De-isolate the relay if it is safe to do so.
3. If no other reason can be found for the fault, replace the faulty ECU main board.
4. Reset the panel.

Device Type Fault

When the system is commissioned the panel notes the device type at each address. If this type
should subsequently change then the panel raises a device type fault.
Indications
Yellow Fault LED is lit.
Fault buzzer sounds.
Event is shown on the display, for example:
TYPE FAULT
Zone 001 Dev 001
Second Floor, Laundry Room
Event is printed (if printer configured).
Issue 1 (01/08/2006)
Event 001
Event 002
Event 001
Doc. No. 503-0800ZE-M-01
Page 9