Extinguishing System Function - Honeywell Notifier ID3000 Manual

Fire panel configuration tool
Hide thumbs Also See for Notifier ID3000:
Table of Contents

Advertisement

CAUTION:
EN
EN
This product is not compliant
12094-1
12094-1
with EN 12094-1.
!
!
Fire extinguishing installations in
Europe are required to be certified
as compliant to this standard.
INPUT
OUTPUT
ALARM
Exting.
(zone or
System
device)
No. n
NON-FIRE
Exting.
(device)
System
No. n
Exting.
Individual
System
Device
No. n
** ID3000 only
ID3000/ID2000 Fire Panel Configuration Tool Manual
ASSOCIATED
PARAMETERS
Release mode
Delay
Soak Time
Co-incidence rules
Abort/Manual/
Off/Hold (mode)/
CO2 Reserve**/
Weight Loss**
Before/after delay
4 - 8

4.1.4 Extinguishing System Function

4.1.4.1 Types of Control Matrix Entry
There are three types of Extinguishing System
Control Matrix entry:
a. Alarm, used to initiate the release in
response to a device or zone in alarm. Up
to 32 separate Extinguishing Systems can
be configured on a panel; the output of the
alarm entry is a reference to one of these.
b. Non-fire, used to configure an Auxiliary
module as a device type unique to
Extinguishing Systems. The output of this
entry is a reference to one of the 32
Extinguishing Systems.
c. Extinguishing, used to activate/deactivate
a device in response to one or more alarm
and non-fire entries. The input of this entry
is one of the 32 Extinguishing Systems.
The 32 available systems work independently
of one another and do not interact. However, it
is possible to configure the same input device
to influence two or more systems, or (less likely
to be used) two or more systems to act on the
same output device.
997-291, Version 3.05
November 2010