RM7888A
OPERATION
Pilot Configuration Operating Sequence.
The Pilot Configuration Operating Sequence has two
distinct operating sequences that are entered from the Stand-
by/Standby Purge states. The sequences are:
a. PV Return: allows the control to reestablish the pilot
and de-energize the main flame in response to the sys-
tem heating requirements.
Pilot
Configuration
State Name
Initiate
Initiate
Initiate
Initiate
Initiate
Initiate
Off
Purge
Control Cool
Low Combustion
Air Only
Pilot Ignition
Main Train
Fuel On
Burner Fuel
Valve Open
(Pilot Timeout)
Release to
Modulation
65-0175
TABLE 5—PILOT CONFIGURATION OPERATING SEQUENCE STATES.
S7800 Keyboard
Display Module
Displayed Text
(See below)
The Initiate state allows the relay module to complete initialization
after a power-up or whenever a problem that would prevent normal
operation (such as an ac line problem), the Initiate state is entered.
INITIATE mm:ss
Displayed during timed portion of the Initiate state.
INITIATE HOLD: AC
Displayed during Initiate state if the ac frequency is low or noise
(AC Freq/Noise)
is present.
INITIATE HOLD: AC
Displayed during Initiate state if the ac line power was lost.
(AC Line Dropout)
INITIATE HOLD: AC
Displayed during Initiate state if the ac frequency is high.
(AC Frequency)
INITIATE HOLD: AC
Displayed during Initiate state if the ac line voltage is low.
(Low Line Voltage)
STANDBY
Remaining idle until valid input(s) are received. All safety loads are
commanded off.
STANDBY HOLD: F/G
Displayed when a flame is detected.
(Flame Detected)
STANDBY HOLD: T7
Displayed when a call for operation is active and the Limits Complete
(Lockout ILK)
signal is off.
PURGE HOLD: T18
Displayed when a call for operation is active and the Low Fire Switch
(Low Fire Switch)
signal is off.
PURGE 01:00
Purge at high fire. All safety loads are commanded off. Display
indicates Purge type 1 = Purge.
PURGE 02:00
Purge at the motor position commanded by the modulating control.
All safety loads are commanded off. Display indicates Purge type
2 = Control Cool.
PURGE 03:00
Purge at low fire. All safety loads are commanded off. Display
indicates Purge type 3 = Low Combustion Air Only.
PILOT IGN mm:ss
Establish a pilot flame. Display shows state and elapsed time. At end
of Pilot Ignition timed state, timer will stop and display will show final
time while a hold exists.
MAIN IGN 00:00
Allow for main valve operators to be placed into the normal operating
condition. Display shows state with zero elapsed time while waiting for
a hold condition(s).
MAIN IGN 00:ss
Establish a main flame and drop the pilot flame. Display will show
MFEP state elapsed time.
RUN
Allow normal operation to take place where a modulating control
provides the motor position signal.
b. MV Lo Fire: will not allow the pilot to be re-estab-
lished once RUN has been entered; the main valve
remains energized with Lo Fire being the lowest firing
rate allowed.
See Table 5 for the state names, the text that appears on
the S7800 Keyboard Display Module, and the purpose.
Purpose of State
20
(Continued)