LCD
GRAPHIC
FUNCTION
DISPLAY
73
ACC PTN
Output
Frequency
Accel

SPECIAL FUNCTIONS

74
N/A
75
ENERGY SAV
76
REV-PH LOC
77
DATA INIT
* 78
LANGUAGE
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
SETTING
ACCELERATION/DECELERATION PATTERN
Selection can be made from the following
types:
0:
Linear acceleration/deceleration (Fig. a)
1:
S curve acceleration/deceleration (Fig. b)
2:
Non-linear for variable torque load (Fig. c)
Fig. A
Output
Frequency
Decel
Accel
Linear
t
NOT USED
ENERGY SAVINGS
Automatically saves energy by weakening
the V/Hz pattern during light load opera-
tion.
0:
Inactive
1:
Active-Volt/Hz ratio is decreased auto-
matically at light loads. Not active
during acceleration or deceleration.
REVERSE DIRECTION LOCK OUT
Prevents the drive from operating in
a reverse direction.
0:
Inactive
1:
Active-Will not allow the motor to run in
reverse direction even in pattern mode.
DATA INITIALIZATION
Allows resetting Function Codes to factory
settings.
0:
Manual setting value (customized drive
settings).
1:
Return to factory default setting values.
LANGUAGE SELECTION
Allows selection of the language in which
the LCD Graphic Display will be shown.
0:
Japanese
1:
English
2:
Spanish
3:
French
DESCRIPTION
Fig. B
Output
Frequency
Decel
Accel
S Curve
t
6-31
FACTORY
SETTING
0
Fig. C
Decel
Non-Linear
t
0
0
0
0
1