Microversatrip� Installation - GE AKR-30 Series Maintenance Manual

Low-voltage power circuit breakers
Hide thumbs Also See for AKR-30 Series:
Table of Contents

Advertisement

The remote fault ind ication switch leads are brought
out the bottom of the M icroVersaTrip program mer as
shown in Fig .
This switch lead harness is pl ugged
78.
i nto the mati ng con nector on the breaker, see Fig . 79.
The switch leads are brought out from the breaker
through the Program mer Secondary Discon nect shown
in Fig .
The zone selective i nterlocking fu nction wir­
80.
i ng is also brought out through this d isconnect. See
Figs. 95 and 96 for the remote fault ind ication and zone
selective i nterlocking cable d iagrams.
• • • •
FIG. 78 MIC ROVERSATRIP W/REMOTE
FAU LT I N DICATION HARN ESS
FIG. 79 PROG RAMMER
SECONDARY CONNECTOR
FIG. 80
REMOTE FAU LT I N D ICATOR
DISC O N N ECT
1 2.1 .3
M ICROVERSATRIP™ I NSTALLATION
The programmer mounts to the u pper left of t he breaker
as shown in Fig. 81 . It mounts to t he bracket assembly
shown in Fig. 82. Referring to Fig. 82, the guide pins mate
with the holes on either side of the programmer connector.
They provide the necessary alig nment for the con nector
engagement . The locking lever engages with the pin which
i s assembled to the programmer frame and secures the pro­
grammer to the mounting bracket
There are two programmer mounting des igns in use. The
d ifference in the des igns is in the operat ion of the locking
lever, see Fig. 82.
I nstal l ation using each design is as follows:
a. I n sert the g u ide pins i nto the holes and push on the pro­
g rammer, engag ing the con nectors.
b. Ori g i nal design -push in the locking lever, securing the
programmer.
Later design-the locking lever is released, securing
the programmer.
c. Verify t hat the locking lever did engage the programmer
pin.
d . Connect remote fault i ndication harness, if eq u i pped,
see Fig. 80.
To remove the programmer:
a. Di sconnect the remote fault ind icat ion harness, if
equi pped.
b. Orig inal designs-push in locking lever, which w i l l
release t h e programmer pin. W h i l e holding the locking lever
in, remove the programmer.
c. Later design-pull out locking l ever, which will release
t he programmer p i n. Remove the programmer.
59