Control panel to drive cable

Use EIA-485 with male RJ-45 connector, cable type Cat 5e or better. The maximum permitted
length of the cable is 100 m (328 ft).

PC tool cable

Connect the Drive composer PC tool to the drive through the USB port of the control panel.
Use a USB Type A (PC) - Type Mini-B (control panel) cable. The maximum length of the
cable is 3 m (9.8 ft).

Routing the cables

General guidelines – IEC
• Route the motor cable away from other cables. Motor cables of several drives can be
run in parallel installed next to each other.
• Install the motor cable, input power cable and control cables on separate trays.
• Avoid long parallel runs of motor cables with other cables.
• Where control cables must cross power cables, make sure that they are arranged at an
angle as near to 90 degrees as possible.
• Do not run extra cables through the drive.
• Make sure that the cable trays have good electrical bonding to each other and to the
grounding electrodes. Aluminum tray systems can be used to improve local equalizing
of potential.
The following figure illustrates the cable routing guidelines with an example drive.
3
min. 200 mm (8 in)
2
1
Motor cable
2
Input power cable
3
Control cable
4
Brake resistor or chopper cable (if any)
Guidelines for planning the electrical installation 97
min. 300 mm (12 in)
2
min. 300 mm (12 in)
2
90°
1
min. 500 mm (20 in)
3
1
4
4
min. 500 mm (20 in)
3