122 Electrical installation
some hardware options, see the circuit diagrams delivered with the drive for the actual
wiring. For other control programs, see their firmware manuals.
Connect the cables as described under

Control cable connection procedure

WARNING!
Obey the safety instructions of the drive. If you ignore them, injury or death,
or damage to the equipment can occur.
1. Stop the drive (if running) and do the steps in section
precautions (page 18)
2. Frames R6 to R9: Remove the cabinet fan and mounting plate above it as described in
section
Connecting the power cables (page 112)
3. Run the control cables into the drive module cubicle as described in section
the outer shields of the control cables at the cabinet entries
4. Route the control cables as described in section
cabinet (frames R6 to R8) (page 124)
(frame R9) (page 125)
R11) (page 126)
5. Connect the control cables as described in sections
cables (page 126)
...
+Q954) (page 132)

Grounding the outer shields of the control cables at the cabinet entry

Ground the outer shields of all control cables 360 degrees at the EMI conductive cushions
as follows (example constructions are shown below, the actual hardware may vary):
1. Loosen the tightening screws of the EMI conductive cushions and pull the cushions
apart.
2. Cut adequate holes to the rubber grommets in the entry plate and put the cables through
the grommets and the cushions.
3. Strip off the cable plastic sheath above the entry plate just enough to ensure proper
connection of the bare shield and the EMI conductive cushions.
4. Tighten the two tightening screws so that the EMI conductive cushions press tightly
round the bare shield.
1
Control cable connection procedure (page 122)
before you start the work.
or
Routing the control cables inside the cabinet
or
Routing the control cables inside the cabinet (frames R10 and
Wiring ground fault monitoring for IT ungrounded systems (option
4
Electrical safety
below.
Routing the control cables inside the
Connecting the control unit
3
2
Grounding